Loading...
HomeMy WebLinkAbout24841 •BDB Engineering Company, LLC; 4' DESIGN ENGINEERING AND INDUSTRIAL SERVICES J 3 P.O.Box 2G207 Phoenix, Arizona 850G8-G207 ! www.bdbencjincering.com Tel:,(,G02) #,1,3-4808, Paxi(623)- 580-8.GG8 February 17, 2006 Client: Southwest Financial of Sun Valley 5630 West Camelback Road Suite 104 Glendale AZ 85301 Project: Permit No: 24841 Southwest Financial of Sun Valley 5630 West Camelback Road Suite 104 Glendale AZ 85301 Re: Ventilation Outside Air Intake Certification, 2003 IMC w/COG Amendments. An investigation was undertaken to examine the ventilation outside air(OSA) intake for the project listed above. The areas of concern investigated were: 1)Comparison of installed equipment capacity with the project requirements . 2)Determination of the following characteristics: a)Total air flow. b)Outside air quantity. The findings are as follows: 1)The OSA balance is in compliance with the applicable Code. 2)The field performance test record is attached for reference. Sincerely, ICA 7-�055�onal En �� m �tiP 161 �m m V 30980 ° TODD A. Cr BUDZIK �J Attachments: Test Record J s r BDB Engineering Comp-an', LLC DESIGN ENGINEERING AND INDU5TRIAL 5ERVIGE5 ' ', 7 m' 3 ; , P.O.Box 2G207 ' Phoenix, Arizona 850G8-G207 www.b6bencjince.rincj.com Tel. (.602) 4 13-4808, Faz'(G 23) 580-8GG8 Ll ,. VENTILATION OSA TEST RECORD Date: 02/17/06 Start 8:15 End 9:30 Client: Southwest Financial of Sun Valley 5630 West Camelback Road Suite 104 Glendale AZ 85301 Project: Permit No 24841 Southwest Financial of Sun Valley 5630 West Camelback Road Suite 104 Glendale AZ 85301 Test Apparatus: Extech Instruments Model 45158 Thermo-Anemometer Dwyer Instrument Model 2000-00AV, 2000-0AV, 2002AV Magnehelic Gage(s). Dwyer Instrument Model 36 Pitot Tube. Test Data Summary: UNIT DESC TOTAL OSA OSA % EAT LAT AIRFLOW REQ'D PROVIDEC TOTAL RETURN SUPPLY (CFM) (CFM) (CFM) OF OF HP-1 2000 195 198 9.9% - - 195 198 - *Required OSA Calculations SF OCC/MSF OSA CFM REQ'D 1236 7 15 130 OCC OSA CFM REQ'D 13 15 195 *Volume Calculations Dim Dim SF Vel CFM 2.75 8.25 0.16 1259 198 1.25 8.25 0.07 1761 126 'BDB Eng Inedhn'g Company, LLC _ } , DESIGN ENGINEERING AND INDUSTRIAL SERVICES = # 1-2 - - 1- P.OrBox t .Phoenix, Arizona 850G8=G207 `' i_` I �` www.bdbengineering.com Tel. (G02) 4I 3;4808;- = Fax (G23) 580-8,GG8 February 17, 2006 Client: Southwest Financial of Sun Valley 5630 West Camelback Road Suite 104 Glendale AZ 85301 Project: Permit No: 24841 Southwest Financial of Sun Valley 5630 West Camelback Road Suite 104 Glendale AZ 85301 Re: Smoke Detector Test Requirement&Certification, 2003 IMC w/COG Amendments. An investigation was undertaken to examine the duct-mount smoke detector inspection and test results performed for the project and permit listed above. The areas of concern investigated were: 1)Verify the duct smoke detectors were installed per plans and specifications. 2)Identify the manufacturer and model of the installed smoke detectors. a)Confirm the installation requirements listed for the smoke detector(s). b)Confirm the differential pressure range listed for the smoke detector(s). c)Confirm the velocity range listed for the smoke detector(s). 3)Field measurements and testing: a)Proper physical installation, pickup tube location and orientation. b)Status/alarm and electrical alarm circuit operational test. c)Differential static pressure test across the smoke detector sensing element. d)Activation test resulting in immediate shutdown upon activation of the smoke detector with aerosol test smoke. The findings are as follows: 1)The smoke detectors have been installed by the contractor in accordance with their listing. 2)The attached Duct Smoke Detector Test Record summarizing the field performance testing as performed and recorded by BDB Engineering Company, indicates acceptable results for the required inspections and tests. Sincerely, �egs�onal En .fie ICA 7- N o 30980 o Nl TODD A. Cr BUDZIK P, j Attachments: BDB Test Record I Air Products &Controls Product Data -i i r _ 5 Y Engineering Compan LLC -- ' _ ; ; i H , DE5IGN,ENGINEERINGAND-INDUSTRIAL�SERVI-E5 �.1 t. i t I I,i �l P.0 6ox.2G207 ;- t t Phoenix, Arizona 850G8-G207 - www.bdben ineenncj Tel. (G02) 4 I-3-4808, fry fax;(623) 580-8GG8 Jwl DUCT MOUNT SMOKE DETECTOR TEST RECORD First Session: Date: 02/17/06 Start 8:15 End 9:30 Second Session: Date: - Start - End - Client: Southwest Financial of Sun Valley 5630 West Camelback Road Suite 104 Glendale AZ 85301 Project: Permit No 24841 Southwest Financial of Sun Valley 5630 West Camelback Road Suite 104 Glendale AZ 85301 Test Apparatus: Detector Manufacturer Installation, Maintenance and Testing Instruction Manual. Fluke Model 77 Multi-Meter. Dwyer Instrument Model 2000-OOAV, 2000-OAV, 2002AV Magnehelic Gage(s). Dwyer Instrument Model36 Pitot Tube. Falcon Safety Products Model DPNXLI2 Compressed Gas Duster. CRC Industries Part #02105 Smoke Test(UL Listed 69G6 Accessory). Detector Data: Firex Model 2650-660 Photoelectric Smoke Detector(Type P) Power Connection: 24 V Pressure Differential Range: 0.01-1.2 WCI Duct Velocity Range: 500-4000 FPM Exceptions: Each smoke detector installation location must be assessed on its own merits in_regards to initial and continuing system performance. Inspection data and test results are recorded for the specific date,time and place identified. These are evaluated to determine whether the system is appropriate and functional under these conditions. Subsequent changes in the smoke detection, air handling, electrical or other related systems may have an effect on the detector installation and performance. Smoke detectors do require periodic maintenance and cleaning every 6 months or quarterly if installed in a dirty environment. Pefer tri manufacturer's literature and recommendations regarding ongoing maintenance. Test Data: 2/17/2006 Unit Desc Detector Status Sample Differential Functional Operational Remote* Type LED Tube Pressure Test Test Accy (WCI) (Smoke) (Shutdown) HP-1 P OK OK(RA) 0.087" Pass (2.7 s) Pass NA *Remote Accessories Codes: NA Not installed NA-B( Not installed -exposed installation NA-FACP Not installed - FACP supervised n6 D`�rl indicator RiuiR Rerno'M indicator& reset i./�Nw ' ii �GTvi� •Yvi�':.vr.T'i.rNAT �.i'.�.`w� ail i't 41 ri„iv�v.`