HomeMy WebLinkAbout62731 ®ffice 6O21141-4727 'UVSt & Balance,16.1,.C. Fax 623-SG9-668 Duct Smoke Detector Test Report Project: Thunderbird Internal Medicine Address: 5620 W. Thunderbird Rd. Glendale, AZ SMOKE DETECTOR ACTUAL ACTUAL SAMPLE SMOKE TEST FIRE PANEL UNIT MANU- MODEL DUCT DIFF. TUBE SHUT OFF TIME ADDRESS/ NUMBER FACTURER Number VELOCITY PRESSURE LENGTH IN SECONDS ZONE PASS FAIL NOTES AC- 1 Air Products SL2000P 850 0.045 Pass 0 N/A x AC-2 Air Products SL2000P 879 0.093 Pass 0 N/A _ x AC-3 Air Products SL2000P 745 0.072 Pass 0 N/A x A ...0°°1 I a I---.'- ',... I t REMARKS: * Design data acquired from information on installed smoke detectors. �0. % . ° `" 0�/ / *Tested with aerosol smoke and testing meets with manufacturers'requirements. °d I ' ` I *Listed Air velocity for smoke detector 100 FPM to 4000 FPM. a t . r i' 1 s *Listed differential pressure: .01 inches to 1.2 inches W.C. 1 ffit *Smoke detectors are not tied to panel at this time. f E ''H< r ��� *Associated systems are a constant volume. T���� ,' *Smoke detectors have been tested prior to air balance. •xp.3 •1112 . co *Verified LED operation. I.,- ROC:215121 1 NEBB:113355 Test Date: 07/06/11 Readings By: MG Page: 1 ,i Clomcgal. Office 602-44 Y-4727 l e5g & Ba1ente ,11.1s.C. F'aax 623-843 c468 Outside Air Summary Report Project: Thunderbird Internal Medicine Address: 5620 W. Thunderbird Rd. Glendale, AZ UNIT OUTLET DESIGN PRELIMINARY FINAL NUMBER TYPE SIZE(IN.) AK VEL CFM VEL CFM VEL CFM NOTES AC- 1 Hood 7.25 x 8.5 .415 422 175 0 0 431 179 AC-2 Hood 7.25 x 8.5 .415 602 250 0 0 621 258 AC - 3 Hood 7.25 x 8.5 .415 904 375 0 0 917 380 TOTAL 800 0 817 A REMARKS: / ;f — -- - *Outside air tested prior to final air balance. i Z 8-..-- �Y. �, I/ r a1►AR io /I C i'f-,F',iItI N Li \ .k. 3': I l'sROC:215121 NEBB:##3355 Test Date: 07/06/11 Readings By: MG Page: 2 a STANLEY Provider of SON1TRC_�•L Products and Services Security Solutions •�. -� .� 7/8/2011 Re: Fire system at Thunderbird Internal Medicine G-2 5620 W Thunderbird Rd. Ste. G-2 Glendale, AZ To Whom It May Concern, This letter is to provide confirmation that all duct detectors for the above-mentioned address have been tied into the fire system,tested, and brought online. For further evidence, please see the attached full zone list of the fire panel. Trouble and supervisory conditions for all 3 duct detectors are reporting at the panel on Zone 5. Please feel free to contact me directly at 480.216.9273 if you have any further questions. Many thanks, Matt Alvey C: 480.216.9273 F:480.393.8273 E:malvev(astanlevworks.com - - -- _ - - -- - Ills No Ins Group Ins Group,� Building I Mon Br Class Pad Br Pad Reg ;,county. MARICOPA STN 8nc�8�H�dvn | ' �� ^ -- ,~_ '—'�_ . jo X. — , ~