RE: ASPERA MOUNTAINSIDE FITNESS
INSPECTORS FIELD COMMENTS
Dear Mr. Bott:
If not required by the City of Glendale building inspector, it is acceptable to remove the two
(2) exit signs located in the Basketball Room from the scope of work.
If you should have any questions or comments regarding the above noted item, please
contact our office.
Sincerely,
Mark Bentley, II
Sr. Electrical Engineer
14-2O6.Itr.1O2715
2050 W.Whispering Wind Pr.,Suite 155, Phoenix,Arizona 6505 -2564—Phone 6 02-255-1669 --Fax 002-255-9450
1
44
/,,,,,zqo
AO��
,..;r:,..7e:_,P - r 4-0 ilfifir --- ,
Hampton Tedder Technical Services
fifchBIcIMSAYS. - n
,fA'AVIEJMS
,...„"ETA
.e GROUND FAULT SYSTEM -
CUSTOMER JFK ELECTRIC INC. JOB NO. TA13585 DATE 9/18/15
JOB LOCATION MOUNTAINSIDE FITNESS AT ASPERA TESTED BY C.DUFF
JOB ADDRESS 20250 N.75TH AVE.GLENDALE,AZ,85308
DATA
EQUIPMENT LOCATION WEST SIDE OF THE BUILDING EQUIPMENT DESIGNATION SES-MSF
SWITCHBOARD MANUFACTURER EATON SO/GO NUMBER SPX0601219
SWITCHBOARD CURRENT RATING 1200 SYSTEM CONFIGURATION RESIDUAL-INTERGRAL
UL NUMBER A 01420475 1 of 3 SYSTEM VOLTAGE 480Y/277
MAIN OVERCURRENT DEVICE
MANUFACTURER EATON TYPE/MODEL NGS
CAT NUMBER/PN NGS312036E CURRENT RATING 1200
GROUND FAULT SYSTEM
MANUFACTURER EATON TYPE/MODEL DIGITRIP 310+
CAT NUMBER/PN NGS312036E SENSOR TYPE/PN BAR TYPE/2608D25G04
CURRENT PICKUP RANGE 250-1200 AMPS TIME DELAY RANGE INST.-300(MS) ®SEC❑CYC
SYSTEM SETTINGS
AS FOUND PICKUP 250 AS LEFT PICKUP 250
AS FOUND TIME DELAY --300(MS) ®SEC❑CYC AS LEFT TIME DELAY 300(MS) 0 SEC 0 CYC
INSPECTION
PHYSICAL AND MECHANICAL CONDITION A NEUTRAL DISCONNECT LINK INSTALLATION A
MAIN BONDING JUMPER INSTALLATION A SENSOR INSTALLATION A
GROUND ELECTRODE CONDUCTOR INSTALLATION A CONTROL POWER TRANSFORMER INSTALLATION NA
A -ACCEPTABLE C -CORRECTED N -NEEDS REPAIR NA -NOT APPLICABLE NS -NOT IN SCOPE
` ELECTRICAL TESTS
PICKUP CURRENT 250 90%PICKUP TEST NO TRIP-CORRECT REACTION TIME NA
PERCENT PICKUP PRIMARY CURRENT TIME DELAY REACTION TIME RELAY TIME
TIME DELAY TESTS 150% 375 0.290 NA NA
200% 500 0.284 NA NA
CPT PRIMARY VOLTS I NA CPT SECONDARY VOLTS NA REDUCED VOLTAGE TEST 55%AC NA
MONITOR PANEL OPERATION NA NEUTRAL SENSOR POLARITY PHASE A A PHASE B A PHASE C A
ZONE SELECTIVE INTERLOCK NA NEUTRAL INSULATION RESISTANCE TO GROUND >4300 MEGOHMS
COMMENTS: NO COORDINATION STUDY ON SITE.BREAKER MATCH ONE-LINE CONFIGURATION.
ALL TESTS YIELDED SATISFACTORY TEST RESULTS.
TEST EQUIP ID/CAL DUE 1 KV MEGGER,CB-832#0726 / 6/18/16
4/05
wn,:` �WI ZRlC TEST
Hamilton Tedder Technical Services �"/► r �"o
`�E pin`,. _inky' t111111r l3 S
GROUND FAULT SYSTEM "' '?
CUSTOMER JFK ELECTRIC INC. JOB NO. TA13585 DATE 9/18/15
JOB LOCATION MOUNTAINSIDE FITNESS AT ASPERA TESTED BY C.DUFF
JOB ADDRESS 20250 N. 75TH AVE.GLENDALE,AZ, 85308
DATA
EQUIPMENT LOCATION WEST SIDE OF THE BUILDING EQUIPMENT DESIGNATION SES-MSF
SWITCHBOARD MANUFACTURER EATON so/GO NUMBER SPX0601219
SWITCHBOARD CURRENT RATING 1200 SYSTEM CONFIGURATION RESIDUAL-INTERGRAL
UL NUMBER A 01420475 1 of 3 SYSTEM VOLTAGE 480Y/277
MAIN OVERCURRENT DEVICE
MANUFACTURER EATON TYPE/MODEL NGS
CAT NUMBER/PN NGS312036E CURRENT RATING 1200
GROUND FAULT SYSTEM
MANUFACTURER EATON TYPE/MODEL DIGITRIP 310+
CAT NUMBER/PN NGS312036E SENSOR TYPE/PN BAR TYPE/2608D25G04
CURRENT PICKUP RANGE 250-1200 AMPS TIME DELAY RANGE INST.-300(MS) I ®SEC 0 CYC
SYSTEM SETTINGS
AS FOUND PICKUP 250 AS LEFT PICKUP 250
AS FOUND TIME DELAY 3OO_(MS)_ _ ®SEC❑_CYC- _AS LEFT TIME DELAY 300(MS) ®SEC❑CYC
INSPECTION .
PHYSICAL AND MECHANICAL CONDITION A NEUTRAL DISCONNECT LINK INSTALLATION A
MAIN BONDING JUMPER INSTALLATION A SENSOR INSTALLATION A
GROUND ELECTRODE CONDUCTOR INSTALLATION A CONTROL POWER TRANSFORMER INSTALLATION NA
A -ACCEPTABLE C -CORRECTED N -NEEDS REPAIR NA -NOT APPLICABLE NS -NOT IN SCOPE
ELECTRICAL TESTS
PICKUP CURRENT 250 90%PICKUP TEST NO TRIP-CORRECT REACTION TIME NA
PERCENT PICKUP PRIMARY CURRENT TIME DELAY REACTION TIME RELAY TIME
TIME DELAY TESTS 150% 375 0.290 NA NA
200% 500 _ 0.284 NA _ NA_
CPT PRIMARY VOLTS I NA CPT SECONDARY VOLTS NA REDUCED VOLTAGE TEST 55%AC NA
MONITOR PANEL OPERATION NA NEUTRAL SENSOR POLARITY PHASE A A PHASE B A PHASE C A
ZONE SELECTIVE INTERLOCK NA NEUTRAL INSULATION RESISTANCE TO GROUND >4300 MEGOHMS
COMMENTS: NO COORDINATION STUDY ON SITE.BREAKER MATCH ONE-LINE CONFIGURATION.
ALL TESTS YIELDED SATISFACTORY TEST RESULTS.
TEST EQUIP ID/CAL DUE 1 KV MEGGER,CB-832#0726 / 6/18/16
4105