HomeMy WebLinkAbout87493 E"1L1(13 ,Je c+e Zl i v $6 f rinci als Kraerner En !ricers, P.L.,L.0 Michael J. Kraemer, P.E. Mechanical brit Electrical Engineers `� -- Richard D. Redmond, P.E. Troy P.Wurth Jason M. bush, James M.Jones,Jr., P.E. October 27, 2015 Mr. Braden Bott LEER AP,Project Manager Ryan Companies US, Inc. 3900 Camelback Road Phoenix, Arizona 85018 RE: ASPERA MOUNTAINSIDE FITNESS INSPECTORS FIELD COMMENTS Dear Mr. Bott: If not required by the City of Glendale building inspector, it is acceptable to remove the two (2) exit signs located in the Basketball Room from the scope of work. If you should have any questions or comments regarding the above noted item, please contact our office. Sincerely, Mark Bentley, II Sr. Electrical Engineer 14-2O6.Itr.1O2715 2050 W.Whispering Wind Pr.,Suite 155, Phoenix,Arizona 6505 -2564—Phone 6 02-255-1669 --Fax 002-255-9450 1 44 /,,,,,zqo AO�� ,..;r:,..7e:_,P - r 4-0 ilfifir --- , Hampton Tedder Technical Services fifchBIcIMSAYS. - n ,fA'AVIEJMS ,...„"ETA .e GROUND FAULT SYSTEM - CUSTOMER JFK ELECTRIC INC. JOB NO. TA13585 DATE 9/18/15 JOB LOCATION MOUNTAINSIDE FITNESS AT ASPERA TESTED BY C.DUFF JOB ADDRESS 20250 N.75TH AVE.GLENDALE,AZ,85308 DATA EQUIPMENT LOCATION WEST SIDE OF THE BUILDING EQUIPMENT DESIGNATION SES-MSF SWITCHBOARD MANUFACTURER EATON SO/GO NUMBER SPX0601219 SWITCHBOARD CURRENT RATING 1200 SYSTEM CONFIGURATION RESIDUAL-INTERGRAL UL NUMBER A 01420475 1 of 3 SYSTEM VOLTAGE 480Y/277 MAIN OVERCURRENT DEVICE MANUFACTURER EATON TYPE/MODEL NGS CAT NUMBER/PN NGS312036E CURRENT RATING 1200 GROUND FAULT SYSTEM MANUFACTURER EATON TYPE/MODEL DIGITRIP 310+ CAT NUMBER/PN NGS312036E SENSOR TYPE/PN BAR TYPE/2608D25G04 CURRENT PICKUP RANGE 250-1200 AMPS TIME DELAY RANGE INST.-300(MS) ®SEC❑CYC SYSTEM SETTINGS AS FOUND PICKUP 250 AS LEFT PICKUP 250 AS FOUND TIME DELAY --300(MS) ®SEC❑CYC AS LEFT TIME DELAY 300(MS) 0 SEC 0 CYC INSPECTION PHYSICAL AND MECHANICAL CONDITION A NEUTRAL DISCONNECT LINK INSTALLATION A MAIN BONDING JUMPER INSTALLATION A SENSOR INSTALLATION A GROUND ELECTRODE CONDUCTOR INSTALLATION A CONTROL POWER TRANSFORMER INSTALLATION NA A -ACCEPTABLE C -CORRECTED N -NEEDS REPAIR NA -NOT APPLICABLE NS -NOT IN SCOPE ` ELECTRICAL TESTS PICKUP CURRENT 250 90%PICKUP TEST NO TRIP-CORRECT REACTION TIME NA PERCENT PICKUP PRIMARY CURRENT TIME DELAY REACTION TIME RELAY TIME TIME DELAY TESTS 150% 375 0.290 NA NA 200% 500 0.284 NA NA CPT PRIMARY VOLTS I NA CPT SECONDARY VOLTS NA REDUCED VOLTAGE TEST 55%AC NA MONITOR PANEL OPERATION NA NEUTRAL SENSOR POLARITY PHASE A A PHASE B A PHASE C A ZONE SELECTIVE INTERLOCK NA NEUTRAL INSULATION RESISTANCE TO GROUND >4300 MEGOHMS COMMENTS: NO COORDINATION STUDY ON SITE.BREAKER MATCH ONE-LINE CONFIGURATION. ALL TESTS YIELDED SATISFACTORY TEST RESULTS. TEST EQUIP ID/CAL DUE 1 KV MEGGER,CB-832#0726 / 6/18/16 4/05 wn,:` �WI ZRlC TEST Hamilton Tedder Technical Services �"/► r �"o `�E pin`,. _inky' t111111r l3 S GROUND FAULT SYSTEM "' '? CUSTOMER JFK ELECTRIC INC. JOB NO. TA13585 DATE 9/18/15 JOB LOCATION MOUNTAINSIDE FITNESS AT ASPERA TESTED BY C.DUFF JOB ADDRESS 20250 N. 75TH AVE.GLENDALE,AZ, 85308 DATA EQUIPMENT LOCATION WEST SIDE OF THE BUILDING EQUIPMENT DESIGNATION SES-MSF SWITCHBOARD MANUFACTURER EATON so/GO NUMBER SPX0601219 SWITCHBOARD CURRENT RATING 1200 SYSTEM CONFIGURATION RESIDUAL-INTERGRAL UL NUMBER A 01420475 1 of 3 SYSTEM VOLTAGE 480Y/277 MAIN OVERCURRENT DEVICE MANUFACTURER EATON TYPE/MODEL NGS CAT NUMBER/PN NGS312036E CURRENT RATING 1200 GROUND FAULT SYSTEM MANUFACTURER EATON TYPE/MODEL DIGITRIP 310+ CAT NUMBER/PN NGS312036E SENSOR TYPE/PN BAR TYPE/2608D25G04 CURRENT PICKUP RANGE 250-1200 AMPS TIME DELAY RANGE INST.-300(MS) I ®SEC 0 CYC SYSTEM SETTINGS AS FOUND PICKUP 250 AS LEFT PICKUP 250 AS FOUND TIME DELAY 3OO_(MS)_ _ ®SEC❑_CYC- _AS LEFT TIME DELAY 300(MS) ®SEC❑CYC INSPECTION . PHYSICAL AND MECHANICAL CONDITION A NEUTRAL DISCONNECT LINK INSTALLATION A MAIN BONDING JUMPER INSTALLATION A SENSOR INSTALLATION A GROUND ELECTRODE CONDUCTOR INSTALLATION A CONTROL POWER TRANSFORMER INSTALLATION NA A -ACCEPTABLE C -CORRECTED N -NEEDS REPAIR NA -NOT APPLICABLE NS -NOT IN SCOPE ELECTRICAL TESTS PICKUP CURRENT 250 90%PICKUP TEST NO TRIP-CORRECT REACTION TIME NA PERCENT PICKUP PRIMARY CURRENT TIME DELAY REACTION TIME RELAY TIME TIME DELAY TESTS 150% 375 0.290 NA NA 200% 500 _ 0.284 NA _ NA_ CPT PRIMARY VOLTS I NA CPT SECONDARY VOLTS NA REDUCED VOLTAGE TEST 55%AC NA MONITOR PANEL OPERATION NA NEUTRAL SENSOR POLARITY PHASE A A PHASE B A PHASE C A ZONE SELECTIVE INTERLOCK NA NEUTRAL INSULATION RESISTANCE TO GROUND >4300 MEGOHMS COMMENTS: NO COORDINATION STUDY ON SITE.BREAKER MATCH ONE-LINE CONFIGURATION. ALL TESTS YIELDED SATISFACTORY TEST RESULTS. TEST EQUIP ID/CAL DUE 1 KV MEGGER,CB-832#0726 / 6/18/16 4105