HomeMy WebLinkAbout1109784 MP di - ENVIRONMENTAL TESTING & BALANCING, INC. r , , HVAC TESTING,ANALYSIS, BALANCING, ENERGY SURVEYS AND AUDITS : °'y February 26,2002 Job: CANYON STATE _ ___ ___575_0AV Thunderbird Rd __-- —-- _--- _ Bldg B,Suite 200 Glendale,Arizona For: A-1 Air Conditioning Duct Smoke Detector Test Report Unit#/Space# Manufacturer L Model Duct size Supply/Return Static Pressure DP Results AC-I INNOVAIR DHI00ACDCI 10 X 48 SUPPLY +.04 PASS AC-2 INNOVAIR DH100ACDCI 10 X 26 SUPPLY +.10 PASS AC-3 INNOVAIR DH100ACDCI 30 X 10 SUPPLY +.02 PASS AC-4 INNOVAIR DHIOOACDCI 10 X 16 SUPPLY +,04 PASS Visual Inspection: ENVIRONMENTAL TESTING&BALANCING certifies to the best of their knowledge that the above smoke detectors are installed as close as possible in accordance to the manufactures recommendation. Due to the slight fluctuations in the pressure readings the above data reflects the lowest readings measured to assure compliance. The flow for the detectors must be greater than .03 DP and not greater than 1.4"DP. • Electrical Inspection: Tested and complies. • --_ - —Eui►cti ii al'rest:— - — - ___ - _ - —- - - -- - - ---— Automatic Shutoff verification completed. All units shut off immediately through the smoke detector when activated by"smoke in a can". Jeremy Hoffman �stlne AABC Certified $ 0 iir p..ia B4L4 % Ij1r // ini 0 � �0 •u. 01-09' TitoMu v r s e ALA ANC 321 W. Hatcher, Ste. 202 • Phoenix,AZ 85021 • (602) 861-1458 • Fax: (602) 861-1864