February 26,2002
Job: CANYON STATE
_ ___ ___575_0AV Thunderbird Rd __-- —-- _--- _
Bldg B,Suite 200
Glendale,Arizona
For: A-1 Air Conditioning
Duct Smoke Detector Test Report
Unit#/Space# Manufacturer L Model Duct size Supply/Return Static Pressure DP Results
AC-I INNOVAIR DHI00ACDCI 10 X 48 SUPPLY +.04 PASS
AC-2 INNOVAIR DH100ACDCI 10 X 26 SUPPLY +.10 PASS
AC-3 INNOVAIR DH100ACDCI 30 X 10 SUPPLY +.02 PASS
AC-4 INNOVAIR DHIOOACDCI 10 X 16 SUPPLY +,04 PASS
Visual Inspection:
ENVIRONMENTAL TESTING&BALANCING certifies to the best of their knowledge that the above smoke detectors are installed as close as
possible in accordance to the manufactures recommendation. Due to the slight fluctuations in the pressure readings the above data reflects the lowest
readings measured to assure compliance. The flow for the detectors must be greater than .03 DP and not greater than 1.4"DP.
• Electrical Inspection:
Tested and complies.
•
--_ - —Eui►cti ii al'rest:— - — - ___ - _ - —- - - -- - - ---—
Automatic Shutoff verification completed. All units shut off immediately through the smoke detector when activated by"smoke in a can".