Loading...
HomeMy WebLinkAbout19511 I rt:i • c' I L� hC I ---i 1 c u Energy Systems Design, Inc, 1 pIEBBCerlificatcFlo.32z3 `tn (602)957-0333 Duct Smoke Detector Test Report I e«h 1 PROJECT Barrucia li LOCATION 5750 W.Thunderbird,Glendale,AZ c an ---______,j GU SMOKE DETECTOR ‘j' ACTUAL ACTUAL SAMPLE FIRE PANEL Nu up,FAN MANU- MODEL DUCT DIFF PRESS TUBE SMOKE TEST ADDRESS/ ea HO. , FACTURER it VELOCITY INCHES W.C. LENGTH SHUT OFF TIME ZONE PASS FAIL NOTES °l- nr AC- 1 A.P.C. S-2000-P �1 40i .09" Pass `'-' 0 Seconds Suite 780 X AC-2 , A.P.C. S-2000-P 472 .12" Pass - 0 Seconds Suite 780 X a a r c } D� i -, I Z� r*z r 3F IT C REMARKS 'Design data acquired from information on installed smoke detectors. � �131 � Tested with aerosol smoke and testing met with manufacturers'requirements. ''S ill s; F4,\ili. r M A (1)Listed Air velocity for smoke detectar..100 FPM to 4000 FPM.H \`��_�_ arm �� '� .I ' i 6LliIEf ' (2)Listed differential pressure:_01 inches'N.C. to 1.2 inches W.C. fAosy'f j -13 D G)l Pic .'� a Readings by:J. Raudebaugh m Test Date:06/27/05 Paugh w TB31-Duct Smoke Deteclorxls i, 06/30/2005 15:22 FAX 602 992 8111 -Wespac Construction uul • WESPAC FAX COVER SHEET CONSTRUCTION INC. • Date: June 30, 2005 From: Derek Ruterman Company: City of Glendale #of Pages: 3 Attn: John Ganka Phone No: 602.956.1323 __ Fax No: ----623-915=2695 - - - -- Re:-~ Barrutia -smoke detectors eifs ❑ Urgent ® For Review ❑ Please Comment ❑ Please Reply • Comments: Attached is the certified duct smoke detector test report for Barrutia Family Medicine on 57'"Ave and Thunderbird. If you have any questions, please contact me at 602-956-1323. Thanks. SIGNED` - Wespac Construction,Inc 9440 N.26"Street-Ste.100'Phoenix,Arizona 85028'602-956-1323/Fax 602-992-8111 Form 7. 06/30/2005 15:22 FAX602 992 8111 titi'espac construction �luuz o_i :���nn� 1C: oL 7L7btle1'L HLF'1Nt MtUrIHNlWHL HAUL d2/03 `"• Energy Systems Design, Inc. . (602)957-6333 Fax(602)954-8393 DUCT SMOKE DETECTOR TEST REPORT SUMMARY PROJECT: Bai,rucia This report represents the final testing of the smoke detectors. The manufacturer's required testing and information data on the safety system has been provided by the installing contractor at the time -- ---of testing-We havewerifiedihat the system-is a constant volume.We have verified that the velocity pick-up tubes in the ductwork are acceptable to manufacturer's requirements. X Does the buildinghave a fire alarm anel? X Have circuits been bypassed? • r X Has central station been called and system put into test mode? i X Mechanical Contractor present? • Fire Alarm Representative present? • X Identified units locations? -- X Noted units names on test form? _ X Units are running? X Have determined how units shut down? ! X , Know how to reset units to power back on? _ X Units manufacturer noted? -, X Have a co of the installation instructions? X Noted units air velocity range? . X Noted units pressure differential? X Verified sampling tube is installed properly? - ' X Housing reinstalled? - X Units are reset and running? - i X Hole plugs, if used have been removed? X Smoke hole entry has been taped? X_Confirmed with.Fire Alarm Rep zone/address reported in alarm? X Noted what smoke detectors operate AHU shutdown or damper closure? . X 1entral station called to remove test status? . X =Applicable If you have any questions, please feel free to call us at (602) 9578333. . 1