s OSA & DUCT DETECTOR REPORT
t.
.........._..
z Project: Corning Gilbert
5310 West Camelback
Glendale, Arizona
�N
MAP Job # 08-1089
MAP TEST.AND
BALANCE
i Architect: T2 Architecture Group, LLC
ri� ,' 7227 North 16th Street, Suite 125
Phoenix Arizona
As
F 4 £} ( g3yg
' f 4'I
?� x `" Y ;f
641 N. Hall f ""k
Engineer: Air-Zona Systems Engineering, Inc.
Mesa, AZ 85203
4531 N. 16th St., Suite 114
Phoenix, Arizona
k 1
� 4 #zQ eS v
r z
9 "i
g�'
General
Contractor: John Bond Contracting
Phone (4$0) 275 6970Y 1 5201 E. Charter Oak Road
`Fax (480) 287 9673 Email
mapta cox net = , , Scottsdale, Arizona
4
1
1 1 I .... ,
x
-,:&-ts-voilAN
a " ..
OSA TEST REPORT P
PROJECT: Corning Gilbert LOCATION: 5310 West Camelback Glendale, Arizona
UNIT SERVED LOCATION DESIGN PREM. FINAL PERCENT NOTES
OSA OSA OSA OF DESIGN
EAC-1 1 Roof 360 371 371 103%
EAC-2 2 Roof 360 380 380 106%.
EAC-3 3 Roof 360 364 364 101%
EAC-4 4 Roof 200 211 211 106%
EAC-5 5 Roof 720 723 723 100%
EAC-6 6 Roof 720 728 •
728 101%
HP-1 7 Roof 200 210 210 105%
HP-2 8 Roof 200 213 213 107%
HP-3 9 Roof 200 215 215 108%
HP-4 10 Roof 600 631 631 105%
11
12
13
14
15
NOTES:
Technician: M.R. Gifford Test Date: April 04, 2008
Page 2
081089-Corning Gilbert
sr
T 3t1. ' " ' ,,,'
1.1
ash st �. . m F 8¢ '�
CERTIFICATION
PROJECT: Corning Gilbert
ADDRESS: 5310 West Camelback
Glendale, Arizona
This report consists of two (2) pages. The cover sheet and this certification are included with this seal.
The data presented in this report is a record of system performance and was obtained in accordance with SMACA and/or ASHRAE standards.
Any variances from design quantities which exceed tolerances are noted throughout this report.
* All duct smoke detectors were tested with aerosol smoke, which met the manufacturer's requirements. The design data was acquired from
the information listed in the manufactures "submittal" which was on site at the time the tests were performed. Installation of the duct
detectors, wiring to fire panel ( if applicable), and all other manufactures installation requirements have been met. Each duct detector has an
audio/visual remote device which signals when the individual duct detector goes into alarm. All duct detectors are interlocked and
when any individual duct detector detects smoke all units within the space shut down.
SUBMITTED BY: Michael R. Gifford CERTIFIED BY: Medhat S. Nakhla
Ve$NonaI En 4,� .
a ,A\FICArey 61
Z.2). 30129
MEDHAT S. a
o,e Sig ne,,
F kk
r _' €
Duct Smoke Detector Test Report
PROJECT: Corning Gilbert LOCATION: 5310 West Camelback Glendale, Arizona
SMOKE DETECTOR VELOCITY FPM DIFFERENTIAL PRESSURE SAMPLE FIRE PANEL SMOKE
FAN NO. INCHES W.C. TUBE ADDRESS/ TEST SHUT PASS FAIL NOTES
LENGTH' ZONE OFF TIME
MANUFACTURER MODEL NUMBER LISTED ACTUAL LISTED ACTUAL
EAC-1 System Sensor DH100ACDCLP 100-4000 295 0.0015 to 1.2 0.33 PASS N/A 0 Seconds X
EAC-2 System Sensor DH100ACDCLP 100-4000 318 0.0015 to 1.2 0.21 PASS N/A 0 Seconds X
EAC-3 System Sensor DH100ACDCLP 100-4000 407 0.0015 to 1.2 0.25 PASS N/A 0 Seconds X
EAC-4 System Sensor DH100ACDCLP 100-4000 241 0.0015 to 1.2 0.24 PASS N/A 0 Seconds X
EAC-5 System Sensor DH100ACDCLP 100-4000 266 0.0015 to 1.2 0.37 PASS N/A 0 Seconds X
EAC-6 System Sensor DH100ACDCLP 100-4000 342 0.0015 to 1.2 0.31 PASS N/A 0 Seconds X
HP-1 System Sensor DH100ACDCLP 100-4000 371 0.0015 to 1.2 0.32 PASS N/A 0 Seconds X
HP-2 System Sensor DH100ACDCLP 100-4000 411 0.0015 to 1.2 0.20 PASS N/A 0 Seconds X
HP-3 System Sensor DH100ACDCLP 100-4000 284 0.0015 to 1.2 0.26 PASS N/A 0 Seconds X
HP-4 System Sensor DH100ACDCLP 100-4000 290 0.0015 to 1.2 0.30 PASS N/A 0 Seconds X
NOTES:
Technician: M.R. Gifford Test Date: April 04, 2008
Page 1 081089-Corning Gilbert
,
- .
�� i. � "<r e 1 awe v �
" , *4•• • *.,,,:: :-5":'ef,,,c;.?. '
OSA TEST REPORT
PROJECT: Corning Gilbert LOCATION: 5310 West Camelback Glendale, Arizona
DESIGN PREM. FINAL PERCENT
UNIT SERVED LOCATION NOTES
OSA OSA OSA OF DESIGN
EAC-1 1 Roof 360 371 371 103%
EAC-2 2 Roof 360 380 380 106%
EAC-3 3 Roof 360 364 364 101%
EAC-4 4 Roof 200 211 211 106%
EAC-5 5 Roof 720 723 723 100%
EAC-6 6 Roof 720 728 728 101%
HP-1 7 Roof 200 210 210 105%
I
HP-2 8 Roof 200 213 213 107%
HP-3 9 Roof 200 215 215 108%
HP-4 10 Roof 600 631 631 105%
11
12
13 i
14
1
15 1
NOTES:
Technician: M.R. Gifford Test Date: April 04, 2008
Page 2 081089-Corning Gilbert