HomeMy WebLinkAbout56236 <>me a, COfficle 60Z-,-vai-racial 605t 82 Beilerliee,10.11-V. Fza.sc 002-3313088 Outside Air Summary Report Project: Edward Jones Address: 20165 N. 67th Ave. Glendale,AZ UNIT OUTLET DESIGN PRELIMINARY FINAL NUMBER TYPE SIZE(IN.) AK VEL CFM VEL CFM VEL CFM I NOTES RTU - 1 Hood 9 x 9 .56 535 300 0 0 510 285 RTU-2 Hood 12 x 8 .66 450 300 0 0 462 307 (1) TOTAL 600 0 592 (1 -�- REMARKS: - - -- *Outside air tested prior to final air balance. e,s"Tes `" (1) No design specified, set at 20% of total design cfrn. ► i it"kr 4 CHA Lro E a.'STALL -,ii.1; rioN +r'' Exp.3/31/12 �Q s\e, it'd ront ROC:215121 NEB8:t13355 Test Date:05/12/10 Readings By:AS Page: 2 N. 'lesati3 i lisete..stee,36•j,.e� Office Ei02-331.E3�D3Z / Fzax Gan-sox-3013a Duct Smoke Detector Test Report Project: Edward Jones Address:20165 N.67th Ave. Glendale,AZ SMOKE DETECTOR ACTUAL ACTUAL SAMPLE SMOKE TEST FIRE PANEL UNIT MANU- MODEL DUCT DIFF. TUBE SHUT OFF TIME ADDRESS/ NUMBER FACTURER Number VELOCITY PRESSURE LENGTH IN SECONDS ZONE PASS FAIL NOTES RTU-1 Air Products SM501 N 1088 0.12 Pass 0 N/A x REMARKS: *Design data acquired from information on installed smoke detectors. `et.,t e: d f *Tested with aerosol smoke and testing meets with manufacturers'requirements. ,, f-- f '� . , *Listed Air velocity for smoke detector 500 FPM to 4000 FPM. t,. *Listed differential pressure: .01 inches to 1.2 inches W.C. f s r Smoke detectors are not tied to panel at this time. t .xN *Associated systems are a constant volume. 4 3 'Smoke detectors have been tested prior to air balance. iexp' 3i/t2 *Verified LED and audible alarm sounds. d �� ROE:215121 NEBB:#3355 Test Date:05/12/10 Readings By:AS Page: 1