Outside Air Summary Report
Project: Edward Jones Address: 20165 N. 67th Ave. Glendale,AZ
UNIT OUTLET DESIGN PRELIMINARY FINAL
NUMBER TYPE SIZE(IN.) AK VEL CFM VEL CFM VEL CFM I NOTES
RTU - 1 Hood 9 x 9 .56 535 300 0 0 510 285
RTU-2 Hood 12 x 8 .66 450 300 0 0 462 307 (1)
TOTAL 600 0 592
(1
-�- REMARKS: - - --
*Outside air tested prior to final air balance. e,s"Tes `"
(1) No design specified, set at 20% of total design cfrn. ►
i it"kr 4
CHA Lro E a.'STALL
-,ii.1; rioN
+r'' Exp.3/31/12
�Q s\e,
it'd ront
ROC:215121 NEB8:t13355
Test Date:05/12/10 Readings By:AS Page: 2
N.
'lesati3 i lisete..stee,36•j,.e� Office Ei02-331.E3�D3Z
/ Fzax Gan-sox-3013a
Duct Smoke Detector Test Report
Project: Edward Jones Address:20165 N.67th Ave. Glendale,AZ
SMOKE DETECTOR ACTUAL ACTUAL SAMPLE SMOKE TEST FIRE PANEL
UNIT MANU- MODEL DUCT DIFF. TUBE SHUT OFF TIME ADDRESS/
NUMBER FACTURER Number VELOCITY PRESSURE LENGTH IN SECONDS ZONE PASS FAIL NOTES
RTU-1 Air Products SM501 N 1088 0.12 Pass 0 N/A x
REMARKS: *Design data acquired from information on installed smoke detectors. `et.,t e: d f
*Tested with aerosol smoke and testing meets with manufacturers'requirements. ,, f-- f '� . ,
*Listed Air velocity for smoke detector 500 FPM to 4000 FPM. t,.
*Listed differential pressure: .01 inches to 1.2 inches W.C. f s
r
Smoke detectors are not tied to panel at this time. t .xN
*Associated systems are a constant volume. 4 3
'Smoke detectors have been tested prior to air balance. iexp' 3i/t2
*Verified LED and audible alarm sounds. d ��
ROE:215121
NEBB:#3355