Outside Air Summary Report
Project: Valley Oximetry Sleep Disorder Center Address: 6320 W. Union Hills Dr. Suite 1000 Glendale, AZ 85308
UNIT OUTLET DESIGN PRELIMINARY FINAL
NUMBER TYPE SIZE(IN.) AK VEL CFM VEL CFM VEL CFM NOTES
AHU- 1 Duct 10 .545 486 265 560 305 501 273
AHU-2 Duct 10 .545 358 195 497 271 369 201
AHU-3 Duct 10 .545 825 450 776 423 862 470
TOTAL 910 999 944
,, ,1
REMARKS:
*Outside air tested prior to final air balance. ... .
,,,,,,,, „4/7/
Ay; „!.: 1,15,
1 it r, f , (
r TALL
�,-1 IFIC *N
i 3355
Exp.3/31/12
,rid'(1)/dronic 5N�'
ROC:215121 NEBB:113355
Test Date: 04/01/10 Readings By: MS Page: 2
CA megga.,
y� .py �7 gyp �tq 7�� 7p- ®9`Yace tsoo-al-Goal.
G st etic tee , !Job•.�. 1y Fux 002-33S-E5®es6
Duct Smoke Detector Test Report
Project: Valley Oximetry Sleep Disorder Center Address: 6320 W. Union Hills Dr. Suite 1000 Glendale,AZ 85308
SMOKE DETECTOR ACTUAL ACTUAL • SAMPLE SMOKE TEST FIRE PANEL
UNIT MANU- MODEL DUCT DIFF. TUBE . SHUT OFF TIME ADDRESS/
NUMBER FACTURER Number VELOCITY PRESSURE LENGTH IN SECONDS ZONE PASS FAIL NOTES
AHU - 1 Air Products SL2000N 898 0.04 Pass 0 101206 x
AHU -2 Air Products SL2000N 426 0.03 Pass 0 101208 x
AHU -3 Air Products SL2000N 789 0.02 Pass 0 101210 x
REMARKS: *Design data acquired from information on installed smoke detectors. sae• e�� /.
Tested with aerosol smoke and testing meets with manufacturers'requirements. �� � � �
* �� e 44"
Listed Air velocity for smoke detector: 100 FPM to 4000 FPM. a, 1
* Listed differential pressure: .01 inches to 1.2 inches W.C. /''
*Associated systems are a constant volume. ^ ( 33,.3
* Smoke detectors have been tested prior to air balance.
*Verified LED. a,7 ~�--.. 5\��
*Verified global shutdown. .'Ydronif
ROC:215121 NE7311:#3355
Test Date: 04/01/10 Readings By: MS Page: 1
‘LHANic
V ��iiii�.
.U•UU\/l1•► l
• aNIM;`MM�NN, r� l
i Ip r„ • Consulting Engineers
tiui 4i_J •
�oM��iTiIIMIr
A..•.UNI000P►
O'SIGNS s
December 22, 2009
C.R. Binder Attn: Craig Binder
4419 W. Port Au Prince Lane
Glendale, AZ 85306 Project: Valley Oximetry
Email: crbroadking49@cox.net West Valley Pharmacy
This letter is written acceptance of a field change to utilize ABS or PVC drain, waste and
vent piping in lieu of the specified cast iron as currently shown on the plumbing
drawings for the above referenced projects.
Should you have any additional questions please feel free to contact our office.
Sincerely,
Justin Grimmett, CPD, LEED AP
MECHANICAL DESIGNS, INC.
.-,.-Qopro.s../ _ _ ________
,0-, /, ); J./. sr,
5 _,95 - '),
� scc, A. •
.4h1ZO1VA,1l, 05 caCARLSO ( ..:,Ai
Expires: 9/30/119,
7227 N. 16th Street, Suite#200 Phoenix, AZ 85020 602.943.6608 FAX 602.943.6181