From: Ptashkin, Mark
Sent: Wednesday, July 11, 2012 2:09 PM
To: Ghahreman, Ed
Subject: FW: Villa Charme Fire
I told them they can call for an inspection when they are complete with their contract. We will final their permit
but will not issue a clearance or a C of O. We will also write on their permit that additional permits will be
required to complete the work and obtain a C of 0/Clearance.
From: Matt Bryant [mailto:matt@valievfireandwater.com]
Sent: Wednesday, July 11, 2012 11:17 AM
To: Ptashkin, Mark
Subject: Villa Charme Fire
Good Afternoon Mark. We are working on a fire restoration of 5727 and 5729 N. 44th Lane. We have a little bit of a unique
situation. There are two separate insurance policies for these homes. The policy that we are working under is through the
H.O.A. and covers damages through drywall. The homeowner's policy covers everything from drywall through finishes.
The homeowners of these units have hired their own contractor to finish their units. The dilemma is that we would like to
be able to close our permit out at the completion of our work. Do you have any suggestions on how I should handle this?
Can we set a temp sink, toilet, and blank off light fixtures to get final or is their a way to revise the permits to show that we
only did rough installation?
Thanks,
Matt Bryant
itj VALLEY
Y IRE 3 lt7f R 5tE'5,1:1RA-IIO,'t
75 W. Baseline Rd. Ste 31
Gilbert, AZ 85233
C: 480-621-1899
P: 480-507-3381
F: 480-507-3857
1
IIISK. YLES
S T RUC RAL
2942 E. Dennisport Ave. Gilbert, AZ 85295 • 480.272.9599
REQUEST FOR INFORMATION RESPONSE
PROJECT: VILLA CHARME 2 STORY PROJECT NO.: 12-025
LOCATION: 5727 N.44TH LANE, GLENDALE,AZ 85301 DATE: 6/26/12
DESIGNER: PALMER DESIGN RFI NO.: 1
CONTRACTOR: VALLEY FIRE, MATT BRYANT
CONCERN:
Please provide a retro-fit alternate for holdown "B" STHD8.
RESPONSE:
Holdown "E" HTT4, on the original plan schedule, shall be used as a retro-fit holdown for missd or mis-installed "B",
STHD8 anchors. At these locations the holdown shall be attached to a double 2x4 post in lieu of the 4x6 post shown
on the schedule. In addition, an epoxy anchor bolt alternate option is provided. Embed a 5/8" diameter threaded rod
6" using Simposn SET-XP epoxy, per Simpson's installation requirements and recommendations.
��tision,g
( aSozICATi%
';;)
LP(//'
3 I
CDAti `_
S X
%
<>orJA, 2
expires 091 °1.\
BY: DANA W. SKYLES, P.E. I 6/26/2012