H.V.A.C. Independent Testing & Balancing Air • Water • Sound • Vibration
Active member of the National Environmental Balancing Bureau (NEBB) Certification No. NF-3129-09
Job: The Orthopedic Clinic Associates P.C. — Suite 185
6320 W. Union Hills Drive - Bldg. B Date: 7-06-06
Glendale, Arizona Page: 1 of 2
TEST CERTIFICATION FOR:
SMOKE DETECTOR AIR PRESSURE DIFFERENTIAL INCLUDING SMOKE
TEST AND EQUIPMENT SHUT DOWN VERIFICATION
Permit#: 28519
Permit Date: May 9, 2006
Sensor Type: Photoelectric Head
Visual Inspection:
Commercial Systems Analysis (CSA) certifies to the best of our knowledge that the following smoke detectors
are installed as close to what is physically possible (due to structural limitations and/or duct configuration) in
accordance to the manufacturer's recommendation. Because of turbulence, there are slight fluctuations in the air
pressure readings, therefore the following data are the lowest readings measured to assure compliance. These
smoke detectors are secured to the duct with the correct length sampling tube properly inserted into the air
stream with a factory red cap in the end.
Electrical Inspection:
The following split system Heat Pump units have one smoke detector installed in the return duct and are
"powered up"with 120 volts supplied through a dedicated circuit from the electrical panel. These smoke
detectors are not being monitored through any fire control panel. A functional remote LED indicator with audible
alarm is installed in the ceiling tile below the respective smoke detector.
Functional Test:
*Airflow verification completed. The following test results(including operating temperature & humidity range
and duct air velocities) are within the manufacturer's specifications. Measurements were taken with an Airdata
Multimeter Model#ADM-870 electronic Micromanometer manufactured by Shortridge Instruments, Inc.
Instrument certification of calibration date is 7-13-05.
**Automatic shutoff verification completed. The following split system Heat Pump units de-energize
immediately through the respective smoke detector when activated using canned smoke.
Special Inspector: Joe Wahl
Kurt M. Wahl
NEBB Qualified
S stemss qs
o\? di
&'(
o L
0i�4 WAH
U AT
3129
Exp.12/31/05
-9� G
�
d dron•lc S�
d 5�
' 10443 N. Cave Creek Road • Ste.207 • Phoenix, Arizona 85020 • (602) 997-8938 • Fax (602) 997-
0 SYYS EMSRCIAL
ANALYSIS R.O.C.#099027
H.V.A.C. Independent Testing & Balancing Air • Water • Sound • Vibration
Active member of the National Environmental Balancing Bureau (NEBB) Certification No. NF-3129-09
Job: The Orthopedic Clinic Associates P.C. - Suite 185
6320 W. Union Hills Drive - Bldg. B Date: 7-06-06
Glendale, Arizona Page: 2 of 2
TEST CERTIFICATION FOR:
SMOKE DETECTOR AIR PRESSURE DIFFERENTIAL INCLUDING SMOKE
TEST AND EQUIPMENT SHUT DOWN VERIFICATION
Required * Actual **Smoke
Unit Make Model Duct Duct Probe Delta Delta Test
Location Width Length Pressure Pressure Results
(Inches w.c.) (Inches w.c.)
AH-1 Air Products SL-2000-P Return 36" 35" .01 - 1.2 .06 Pass
& Controls
AH-2 Air Products SL-2000-P Return 19" 17" .01 - 1.2 .01 Pass
& Controls
AH-3 Air Products SL-2000-P Return 36" 38" .01 - 1.2 .03 Pass
& Controls
AH-4 Air Products SL-2000-P Return 36" 38" .01 - 1.2 .01 Pass
& Controls
AH-5 Air Products SL-2000-P Return 36" 38" .01 - 1.2 .03 Pass
& Controls
\��S stems 4
e NEAR �N
U
,d fa tFiritcoL6 i ..
3129
Exp.12/31/05
0
10443 N. Cave Creek Road • Ste. 207 • Phoenix, Arizona 85020 • (602) 997-8938 • Fax (602) 944. 9Q-t,n;c 5�5�
COMMERCIAL Page 1 of 1
• ``) SYSTEMS
ANALYSIS
AIR CONDITIONING UNIT OSA TEST
PROJECT: The Orthopedic Clinic Associates P.C. - Suite 185
ADDRESS: 6320 W. Union Hills Drive, Bldg. B
CITY, STATE Glendale, Arizona DATE: 07-06-06
TECHNICIAN: JW
MAKE/MODEL# UNIT DESIGN PRELIMINARY FINAL
SERIAL# NO. SIZE "K" FPM CFM FPM CFM FPM CFM NOTES
Trane /TWE060A400EL AH-1 10"0 .54 370 200 618 334 388 209
545654MBD
Trane /2TEC3F36A1000AA AN-2 10"0 .54 185 100 580 313 193 104
54247DEIV
Trane / TWE060A400EL AH-3 10"0 .54 370 200 800 432 396 213
5454NH6BD
Trane / TWE060A400EL AH-4 10"0 .54 370 200 514 277 382 206
5434L5BBD
Trane / TWE060A400EL AH-5 10"0 .54 370 200 791 427 386 208
5454NJCBD
Total 900 1783 940