HomeMy WebLinkAbout63437 n Engineering,LLC V v1 t (o313l August 2, 2011 Attn: Dave Drazy Construction Manager, Nextcare Re: Nextcare Glendale Lobby TI Mr. Drazy- We understand that for the project listed above, the electrical conduit for branch circuit wiring has been installed as type MC cable in lieu of EMT as specified on the drawing. We accept the installation of MC type cable for the branch circuits as long as the electrical inspector does not see any code violations with the installation. Secondly,we understand that the telecom conduits installed from the ceiling down the wall to the reception desk have been installed to meet Nextcare's needs and requirements. It is not necessary by any code to install a certain quantity of telecom conduits, a certain size of telecom conduits, or is it necessary to install a separate conduit to each telecom device in the reception desk. If the installation was able to meet the owner's needs utilizing (2)conduits down the wall, then we accept that installation and there is no code violation. Please call me @ 480-275-2588 for additional clarification. Thank you Sincerely, Gary D. Stringer, PE ' '39541t Principal , w eARY 0; err ices 9j30/ez • Stringer Engineering,LLC 4540 E.White Aster St.+Phoenix,AZ 85044 4-Phone 480-275-2588+Fax 480-275-2589 \\Stringer server\Projects\SPG\SPG_11 03\Letter for Value Eng.doc