Duct Smoke Detector tea. c�
Operational Test o
• to
AABC Certified o
TAB Technology,Inc. / / o
4627 East Ivy,Ste.#3,Mesa,Az 85205 m
Office: 480-964-0187 .j. ,'' .l't:ti Page: 1 w
Fax: 480-964-0274 m
4 32388 -
Project: Simonmed Imaging Engineer: Associated Mechanical Engineers I GEORGE J. 3
Location: 5410 W.Thunderbird Road Contact: George Josephs JOSE` 1• •+
Glendale,Arizona 85306 Office: 480-966-3996 • .. I`R -
q d1: 0
Date: 8-Aug-06 General Contractor. 4ii<o NA 11� to
Contact: - -+
Technician: Phil Hoyt Office Number. ri
m
I
Manufacture: Air Products&Controls Mechanical Contractor:KBK Mechanical Michael Ziegler 2
0
Model#: SM-501-N Contact Barry Test and Balance Engineer r
Office: 623-939 0220 Certificate#98-01-42 0o
EWSIIP�i Model#: SL-2000-N -C
{
Unit ID Required Required Duct Size Final Final Installed per Blower Smoke Zone Audible Visual Fire Alarm
Device Pressure and Device Pressure Manuf.Listing Shut-down AC Units Alarm Alarm System
Flow Range Differential Tube Length Flow Range Differential (Yes/No) (Yes/No) (Yes/No) Pass/Fail Pass/Fail (Yes/No)
(FPM) In WG) (FPM) (In WG) 'Note 1] ote 21 JNote 3] ote 4
WSHP-1 400 to 4000 0.01 to 1.20 16"/14" 694 0.030 Yes Yes N/A Yes Yes , No
WSHP-2 400 to 4000 0.01 to 1.20 _ 24"/22" 491 _ 0.015 Yes Yes N/A Yes Yes No
WSHP-3 400 to 4000 0.01 to 1.20 15"/16" 658 0.027 Yes _ Yes N/A Yes Yes No
EWSHP-4 400 to 4000 0.01 to 1.20 20"/18" 821 0.042 Yes Yes N/A Yes Yes No
_ EWSHP-5 400 to 4000 0.01 to 1.20 22"/24" 420 _ 0.011 Yes Yes N/A Yea Yes No 0
EWSHP-6 100 to 4000 0.01 to 1.20 20"/18" 283 _ 0.005 Yes Yes N/A Yes Yes No
EWSHP-7 400 to 4000 4_ 0.01 to 1.20 20"/19" 1119 0.078 Yes Yes N/A _ Yes Yes No COcn
EWSHP-9 400 to 4000 0.01 to 1.20 18/16" 537 0.018 Yes Yes N/A Yes _ Yes No 4
EWSHP-11 400 to 4000 0.01 to 1.20 14 x 20/ IS" 1140 0.081 Yes _ Yes N/A Yes Yes No
FCU-6 400 to 4000 0.01 to 1.20 14 x 20/19.5" 1060 0.070 Yes Yes N/A Yes Yes IMINRIIIMM I
Notes:
1. Includes verification that location and length of smoke testing probe meets manufacturer's recommendations.
2. Each Duct Smoke Detector was tested with canned chemical smoke,Smoke Detector Tester,Model No.25 S,to assure unit shutdown.
Includes verification that any manufacture's fan shutdown delay for economizer operation has been bypassed for immediate shutdown by signal from detection device.
•
3. Each detection device within the smoke zone was tested separately with verification that each AC unit blower within that smoke zone shuts down upon initiation of the
device. The system was then reset and tested for each device within the smoke zone.
4. Fire alarm system per LMC Section 606.4.1. Exception 2.without fire alarm system see Audible and Visual alarm columns.
5. TAB Technology states the readings are accurate at the time of testing. -a
6.6. TAB Technology recommends that the smoke detectors are maintained per manufactures recommendations and are tested every six months N
Aug 07 06 06: 50p p. 1
ASSOCIATED
MECIIANICAL
ENGINEERS, PLC.
1505 West University, Ste. 101
Tempe, Arizona 85281
CONSULTING ENGINEERS
MECHANICAL ♦ PLUMBING
FACSIMILE TRANSMITTAL
This facsimile and all the contents herein are the sole property of Associated Mechanical Engineers and are
intended for the recipient named above. if you have mistakenly received this facsimile or are unable to deliver the
material to the intended recipient please contact our offices immediately 480.966.3996.
Date: August 7, 2006
Firm Name: KBK Mechanical
Fax Number: 623-847-9829/623-487-1246
Attention: Ken Stucks/Larry Tennant
From: Brett Johnson
Referencing: SimonMcd-Glendale Page: 1 of 1
AME Job Number: 05-182 Original to Follow: Oyes Ono
Remarks:
Ken/Larry,
In regards to the cryogen vent material, size, and insulation: Larry Tennant was instructed by us
to run 8"pipe until it turns vertical,then transition to 10" for the remainder of the run.
Aluminum pipe is also an acceptable material. Per Kent Conrad's(G.E.) input, only the portions
of cryogen vent within the MRI room need to be insulated with 1-1/2"Armaflcx, and is therefore
acceptable to us. In regards to the 02 sensor: Kent Conrad (G.E.) again has regarded this as an
item that is not required. Per his recommendations,we are allowing the omittance of this item.
Please feel free to contact our office with any questions or concerns.
Thank you, 7 � c)9 ,7
Brett Johnson 3
-- 4 -4r` :\
4 , • rE ;c‘+►�.
t 32308 ';‘
GEORGE J, • �is
JOSEPHS I
Ass•ociatcd Mechanical Engineers, PLC. % • 110
480.966.3996 phone •480.966.3964 ftx•www-am-engineers.co 't. ,a V17 .