HomeMy WebLinkAbout00000 (5) i
f � o, ^r t'J
ll-
i- - ; ' ' — '' Project: Little Caesars
10240 N. 43rd Ave.
Glendale, Arizona
i'l:;'''''''''''''':.4 - MAP Job # 10-1846
i
�4 ez :,4,1yr r `rr
S�# rt Py'M TES
TANDALBAANCE i';''''''
v Architect: ArizaDo Architecture
6910 E. Chauncey Ln., Suite 105
Phoenix, Arizona
1
641 N. Ha11
1VIesa, 'AZ 85203 ' Engineer: ArizaDo Architecture
6910 E. Chauncey Ln., Suite 105
Phoenix, Arizona
k d k 1
[- ,
t L ` I➢'
Mechanical
Contractor: L&H Mechanical
Cell (480)69576314, 4038 E. Superior Ave.
Fax:(480)287=9673 Bldg. #2 Suite 103
Email:.thebest:@rnaptab cdm t.
Phoenix, Arizona
A
CERTIFICATION
PROJECT: Little Caesars
ADDRESS: 10240 N. 43rd Ave.
Glendale, Arizona
THE DATA PRESENTED IN THIS REPORT IS A RECORD OF SYSTEM PERFORMANCE AND WAS OBTAINED IN ACCORDANCE WITH
ASHRAE STANDARD 111-2008 FOR MEASUREMENT, TESTING, ADJUSTING, BALANCING OF BUILIDING HVAC SYSTEMS . THE AIR
VELOCITY IN THE INSTALLED 18 x 18 DUCTWORK IS 693 WHICH MEETS OR EXCEDES DESIGN PARAMETERS.
THE AIR AND/OR WATER DISTRIBUTION SYSTEMS HAVE BEEN TESTED, BALANCED AND FINAL ADJUSTMENTS HAVE BEEN MADE IN
ACCORDANCE WITH ASHRAE STANDARD 111-2008 FOR MEASUREMENT, TESTING, ADJUSTING, BALANCING OF BUILIDING HVAC
SYSTEMS AND THE PROJECT SPECIFICATIONS
SUBMITTED & CERTIFIED BY: Michael R. Gifford
�PQ.cssi&BALL
Ce ed11)01P
0
C'Sae1 �
1 ,
. , .
. . ..,...,,, ... ,,,,
, .
ID;
. „.. .....„,. ,-,-„ , „ ..,.,
, „.
n. h
;yA
PROJECT: Little Caesars
UNIT NUMBER: RTU-1 LOCATION: M-1
UNIT DATA MOTOR DATA
Manufacturer Trane Make/Frame GE / 56
Model Number WSC090A3RoAoF HP/RPM 1 / 1725
Serial Number 225100863L Volts/Phase 208-230/460 / 3
Fan Sheave Make Browning F.L. Amps/S.F. 3.2-4.0/2.0 / 1.15
Fan Sheave Diam./Bore AK59 x 1" Make Sheave Browning
No. Belts/Size 1 / A32 Sheave Diam./Bore 1VL40 x 5/8"
# Filters/Size 4 / 16" x 25" x 2"
TEST DATA TEST DATA
EVAPORATOR DESIGN ACTUAL CONDENSER DESIGN ACTUAL
Total CFM 2,000 2,175 Compressor Volts 208-230 210
External Static Pressure 0.50" 0.53" Compressor Amps 26.0 22.8
Discharge S.P. inches W.C. --- 0.36" Condenser Fan HP 7/10 7/10
Suction S.P. inches W.C. --- -0.17" Condenser Fan Volts 208-230 210
Return Air CFM 1775 1,946 Condenser Fan Amps. 2.90 2.37
Outside Air CFM 225 229 Condenser Fan RPM 1100 DD
Entering Air Temperature --- 76°F
Leaving Air Temperature --- 56°F
Fan RPM --- 1072 *For all other refrigeration, compressor, and
Voltage 208 210 condenser test data see start-up report from
Amperage 3.20. 2.96 the installing contractor and/or supplier
Notes:
Test Date: April 5, 2010 Tech: M.R. Gifford
101846-Little Caesars @ Glendale Page 1
, 4
t x"C
4
AIR OUTLET/INLET TEST REPORT
PROJECT: Little Caesars
UNIT NUMBER: RTU-1 LOCATION: 'M-1
OUTLET DESIGN PREM. FINAL PERCENT
AREA SERVED NOTES
NO. TYPE SIZE CFM CFM CFM OF DESIGN
Lobby 100 1 CD 24" x 24" 400 602 441 110%
Lobby 100 2 CD 24" x 24" 400 541 437 109%
Lobby 100 3 CD 24" x 24" 400 569 433 108%
Lobby 100 4 CD 24" x 24" 400 419 436 109%
Lobby 100 5 CD 24" x 24" 400 374 428 107%
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
TOTAL 2,000 2,505 2,175
NOTES:
Test Date: April 5, 2010 Tech: M.R. Gifford
101846-Little Caesars @ Glendale Page 2
aim-J.. �.�;. - .t11'G7/—�,`C{ '
Sys 4 :, {S + i •• 'a.. 7
cgu
PROJECT: Little Caesars
UNIT NUMBER: RTU-2 LOCATION: M-1
UNIT DATA MOTOR DATA
Manufacturer Rheem Make/Frame (1)
Model Number RKNL-A060L10E HP/RPM 3/4 / 1725
Serial Number 2G7503ADAAF Volts/Phase 208-230/460 / 3
Fan Sheave Make Browning F.L. Amps/S.F. 3.4/2.7 / 1.15
Fan Sheave Diam./Bore AK66 x 3/4" Make Sheave Browning
No. Belts/Size 1 / A42 Sheave Diam./Bore 4" O.D. x 5/8"
# Filters/Size 2 / 16" x 25" x 2"
TEST DATA TEST DATA
EVAPORATOR DESIGN ACTUAL CONDENSER DESIGN ACTUAL
Total CFM 2,000 1,858 Compressor Volts 208-230 210
External Static Pressure 0.50" 0.53" Compressor Amps 15.6 14.3
Discharge S.P. inches W.C. --- 0.32" Condenser Fan HP 1/3 1/3
Suction S.P. inches W.C. --- -0.21" Condenser Fan Volts 208-230 210
Return Air CFM 1775 1,624 Condenser Fan Amps. 1.80 1.46
Outside Air CFM 225 234 Condenser Fan RPM 1075 DD
Entering Air Temperature --- 77°F
Leaving Air Temperature --- 56°F
Fan RPM --- 948 *For all other refrigeration, compressor, and
Voltage 208 210 condenser test data see start-up report from
Amperage 3.40 3.17 the installing contractor and/or supplier
Notes: (1) Nameplate is not visible.
Test Date: April 5, 2010 Tech: M.R. Gifford
101846-Little Caesars @ Glendale Page 3
mil Cr y.
A. #..#7.. #1' r k,
n.
Ik� ' ydf,�,
AIR OUTLET/INLET TEST REPORT
PROJECT: Little Caesars
UNIT NUMBER: RTU-2 LOCATION: M-1
OUTLET DESIGN PREM. FINAL PERCENT I
AREA SERVED NOTES
NO. TYPE SIZE CFM CFM CFM OF DESIGN
Backroom 102 1 CD 24" x 24" 400 374 374 94%
Backroom 102 2 CD 24" x 24" 400 392 392 98%
Backroom 102 3 CD 24" x 24" 400 368 368 92%
Backroom 102 4 CD 24" x 24" 400 360 360 90%
Backroom 102 5 CD 24" x 24" 300 273 273 91%
Restroom 103 6 CD 12" x 12" 100 91 91 91%
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
TOTAL 2,000 1,858 1,858
NOTES:
Test Date: April 5, 2010 Tech: M.R. Gifford
101846-Little Caesars @ Glendale Page 4
may, .0y
xis {{{"��� yet 1 r `
,R.,�� {{{'4
orb , 4 - , w: ,A, ,..
,Ii
r *41 6
Toilet Exhaust Fans
PROJECT: Little Caesars
EF-1
Location Ceiling
Service Restroom 103
Design CFM 100
Actual CFM 108
NOTES:
Test Date: April 5, 2010 Tech: M.R. Gifford
101846-Little Caesars @ Glendale Page 5
C
'°.tip..:
Fan
PROJECT: Little Caesars
FAN DATA EF-2 MAU-1
Location Roof Roof
Service Kitchen Hood Kitchen Hood
Manufacturer Accurex Aaon
Model Number XRUB-141-5-6 RMA-05-8-0-BB01
Serial Number 11927358 0912 200908-AMCE07174
Motor Make/Frame Marathon / 48Y Marathon / 56HZ-70
Motor HP / Phase / RPM 1/2 / 1 / 1725 1 / 3 / 1725
Volts/Amps 115 / 7.5 208-230/460 / 3.5-3.6/1.8
Motor Sheave Make Browning Browning
Motor Sheave Diam./Bore 1VP34S x 1/2" 1VP44 x 7/8"
Fan Sheave Make Browning Browning
Fan Sheave Diam./Bore AK46 x 3/4" BK62 x 1"
No. Belts/Size 1 / AP20 1 / BX48
FAN TEST DATA DESIGN ACTUAL DESIGN ACTUAL
CFM 1380 1472 1380 1329 '
Fan RPM --- 1054 856 1011
External S.P. --- .53" 0.75" 0.69"
MOTOR TEST DATA VOLTAGE AMPS VOLTAGE AMPS
T-1/T-2 117 7.26 210 i 3.21
T-2/T-3
T-1/T-3
NOTES: Area Velocity Design Actual
1.25 747 Prep 101 480 471
Area Velocity Prep 101 450 436
1.25 725 Prep 101 450 422
Test Date: April 5, 2010 Tech: M.R. Gifford
101846-Little Caesars @ Glendale Page 6
f,,i y+..
AIR BALANCE SCHEDULE
PROJECT: Little Caesars
UNIT SERVED LOCATION DESIGN ACTUAL DESIGN ACTUAL PERCENT
EF CFM EF CFM OSA CFM OSA CFM OF DESIGN
EF-1 1 Roof 100 108 108%
EF-2 2 Roof 1380 1472 107%
3
TOTAL 1480 1580
MUA-1 1 Roof 1380 1329 96%
RTU-1 2 Roof 225 229 102%
RTU-2 3 Roof 225 234 104%
TOTAL 1830 1792
Test Date: April 5, 2010
Tech: M.R. Gifford
Page Caesars @ Glendale gge 7
N., fir ..,,,
5, Ak '
4kr
Duct Smoke Detector Test Report {{{{{f..;..:Li,"
111.-t.:,:;4.14.. .":_;-. -,,,\:Tn:,;,..,14.5.;
PROJECT: Little Caesars LOCATION: 10240 N. 43rd Ave. Glendale, Arizona
SMOKE DETECTOR VELOCITY FPM DIFFERENTIAL PRESSURE SAMPLE FIRE PANEL SMOKE
FAN NO. INCHES W.C. TUBE ADDRESS/ TEST SHUT PASS FAIL NOTES
LENGTH ZONE OFF TIME
MANUFACTURER MODEL NUMBER LISTED ACTUAL LISTED ACTUAL
RTU-1 Air Products SL-2000-N 100-4000 358 .01 to 1.2 0.09 PASS Supv. Only 0 Seconds X
RTU-2 Air Products SL-2000-N 100-4000 312 .01 to 1.2 0.11 PASS Supv. Only 0 Seconds X
NOTES: * All duct smoke detectors were tested with aerosol smoke, which met the manufacturer's
requirements. The design data was acquired from the information listed in the manufacturer's
"submittal" which was on site at the time the tests were performed. Installation of the duct detectors, T&g
wiring to fire panel ( if applicable), and all other manufacturer's installation requirements have been „79,__� A •,Y�•,,
met. Each duct detector has an audio/visual remote device which signals when the individual11
duct detector goes into alarm. f 1
* /
Certifies }
/ i
�r'�Da '`
.c �o,
haei�G�.
MAP Test and Balance, LLC
Technician: M.R. Gifford 641 N. Hall, Mesa, AZ 85203 Test Date: April 5, 2010
Page 1- 101846-Little Caesars @ Glendale
, .
._ ,
. , .
. .
T rio,
k . 1,
, - t N .:.
...„..,
...,,,, Fa 1 T I Att,
, ;„. L
DATE: 30 December 2009
IH
TO: Frontera Building Cornpan ,LLC
4110 N. Scottsdale Road ...
Suite 125
Scottsdale,AZ 85251
Attn: Ben Irwin
FROM: Chris Cooper A LA
RE: Little Caesars
10240 N 43rd Avenue
Glendale, Arizona 85302
CC: File
Ben,
Please accept this letter as written acceptance for the use of'underground type I.'piping.
Construction will need to be in conformance with all apol:cable codes and requirements
If you should Rate any questions or comments please call me Thank you
)
Id
, icooPER 4
'1.. \,Z.,--i•41-'::
Arizapo
f,i1111z,gl 1:117,kvinv iiifT Si, 05 Piwenly Prfr'ina 4iii?7E8?Mil p"430 7.58 MI5 f
Ment2r I C C •liff,A. -IESC -4.1:,