January 19, 2012
City of Glendale
Attn: Electrical Building Inspector
Re: Nextcare @ 43rd Ave
Dear Building Inspector
The original electrical design for this project called for dedicated neutral conductors for each
120V, 20A 1 pole branch circuit from Panels L1 & L2. It has been requested from the electrical
contractor for this project that several 120V, 20A, 1 pole branch circuits from Panels L1 & L2 be
allowed to share a neutral conductor. We have reviewed the request as follows:
Panel L1 —circuits 10, 12, 14 share (1) neutral conductor
Panel L1 —circuits 25, 27 share (1) neutral conductor
Panel L1 —circuits 30, 32 share (1) neutral conductor
Panel L1 —circuits 34, 36 share (1) neutral conductor
Panel L1 — circuits 16, 18, 20 share (1) neutral conductor
Panel L2—circuits 16, 18, 20 share (1) neutral conductor
Panel L2 —circuits 22, 24, 26 share (1) neutral conductor
We understand that the City of Glendale is enforcing to the 2005 NEC. We accept the request
to share the neutral conductor for the circuits listed above.