Loading...
HomeMy WebLinkAbout66263 tt- cf'Lf- ' (V\V1�rirLger Engineering,LLC 8LBLh1CAL®JGJ®PP O&DESIGN January 19, 2012 City of Glendale Attn: Electrical Building Inspector Re: Nextcare @ 43rd Ave Dear Building Inspector The original electrical design for this project called for dedicated neutral conductors for each 120V, 20A 1 pole branch circuit from Panels L1 & L2. It has been requested from the electrical contractor for this project that several 120V, 20A, 1 pole branch circuits from Panels L1 & L2 be allowed to share a neutral conductor. We have reviewed the request as follows: Panel L1 —circuits 10, 12, 14 share (1) neutral conductor Panel L1 —circuits 25, 27 share (1) neutral conductor Panel L1 —circuits 30, 32 share (1) neutral conductor Panel L1 —circuits 34, 36 share (1) neutral conductor Panel L1 — circuits 16, 18, 20 share (1) neutral conductor Panel L2—circuits 16, 18, 20 share (1) neutral conductor Panel L2 —circuits 22, 24, 26 share (1) neutral conductor We understand that the City of Glendale is enforcing to the 2005 NEC. We accept the request to share the neutral conductor for the circuits listed above. If any further clarification is required, we may be contacted at 480-390-5127. Thank you. Sincerely st-loonsi ky 354101f; GA Gary D. Stringer 1.5 RIG R . ;rat '/3c)/t z. Stringer Engineering, LLC 4540 E.White Aster St. + Phoenix,AZ 85044♦Phone 480-275-2588 +Fax 480-275-2589 \\Stringer_server\Projects\SPG\SPG_11_06\Letter for Neutral Conductor.doc