Duct Smoke Detector Test Report
Project: Next Care Urgent Care Address: 10240 N.43rd Ave. Suite 103 Glendale,AZ 85032
SMOKE DETECTOR ACTUAL ACTUAL SAMPLE SMOKE TEST FIRE PANEL
UNIT MANU- MODEL DUCT DIFF. TUBE SHUT OFF TIME ADDRESS/
NUMBER FACTURER Number VELOCITY PRESSURE LENGTH IN SECONDS ZONE PASS FAIL NOTES
HP-2 Air Products SL2000P 846 0.31 Pass 0 N/A x
HP-3 Air Products SL2000P 790 0.29 Pass 0 N/A x
I
-
; n - _ n
REMARKS: * Design data acquired from information on installed smoke detectors, r , --_•_�°-;ry;".
"Tested with 4rosol smoke and testing meets with manufacturers'requirements. t w :
' Listed Air velgcity for smoke detector 100 FPM to 4000 FPM. �i' fr # r- •ipmft ',
* Listed differential pressure: .01 inches to 1.2 inches W.C.
r( i 1
*Associated systems are a constant volume. r� i
*Smoke detectors have been tested prior to air balance. ;> / s
_ �
'Verified LED tnd audible alarm sounds. 1 �` •. iti,).:,,1." ' >1 ' r. �'.
' �' 4'f'
r;?
ROC:215121 i
NEBB:#3355
Test Date:01/17/12 Readings By: CH Page: 1
r
I
•
MMegn Office 6o2-441-4727
"GeSt & Beii ee ,L.L.e. Fax 6. 3-869-a>468
Outside Air Summary Report
Project: Next Care Urgent Care Address: 10240 N. 43rd Ave. Suite 103 Glendale, AZ 85032
UNIT OUTLET DESIGN PRELIMINARY FINAL }
NUMBER TYPE SIZE(IN.) AK VEL CFM VEL CFM VEL CFM NOTES
HP-1 Hood 7 1/4 x 8 1/2 .43 348 150 285 123 362 156
HP-2 Hood 7 1/4 x 8 1/2 .43 348 150 236 101 376 162
HP-3 Hood 7 1/4 x 8 1/2 .43 581 250 253 109 599 258
TOTAL 550 333 576
----
REMARKS:
r'
i
I(
C�' T ' 3i2 2 fI 1
ROC:215121
NEBB:#3355
Test Date: 01/17/12 Readings By: CH Page: 2