Loading...
HomeMy WebLinkAbout66262 i od a® 4sa �� ic. z- 44 -47z7 'Gest a seg1 e. ,Ls1...iJ(�e Fnx 4323-St39 s468 Duct Smoke Detector Test Report Project: Next Care Urgent Care Address: 10240 N.43rd Ave. Suite 103 Glendale,AZ 85032 SMOKE DETECTOR ACTUAL ACTUAL SAMPLE SMOKE TEST FIRE PANEL UNIT MANU- MODEL DUCT DIFF. TUBE SHUT OFF TIME ADDRESS/ NUMBER FACTURER Number VELOCITY PRESSURE LENGTH IN SECONDS ZONE PASS FAIL NOTES HP-2 Air Products SL2000P 846 0.31 Pass 0 N/A x HP-3 Air Products SL2000P 790 0.29 Pass 0 N/A x I - ; n - _ n REMARKS: * Design data acquired from information on installed smoke detectors, r , --_•_�°-;ry;". "Tested with 4rosol smoke and testing meets with manufacturers'requirements. t w : ' Listed Air velgcity for smoke detector 100 FPM to 4000 FPM. �i' fr # r- •ipmft ', * Listed differential pressure: .01 inches to 1.2 inches W.C. r( i 1 *Associated systems are a constant volume. r� i *Smoke detectors have been tested prior to air balance. ;> / s _ � 'Verified LED tnd audible alarm sounds. 1 �` •. iti,).:,,1." ' >1 ' r. �'. ' �' 4'f' r;? ROC:215121 i NEBB:#3355 Test Date:01/17/12 Readings By: CH Page: 1 r I • MMegn Office 6o2-441-4727 "GeSt & Beii ee ,L.L.e. Fax 6. 3-869-a>468 Outside Air Summary Report Project: Next Care Urgent Care Address: 10240 N. 43rd Ave. Suite 103 Glendale, AZ 85032 UNIT OUTLET DESIGN PRELIMINARY FINAL } NUMBER TYPE SIZE(IN.) AK VEL CFM VEL CFM VEL CFM NOTES HP-1 Hood 7 1/4 x 8 1/2 .43 348 150 285 123 362 156 HP-2 Hood 7 1/4 x 8 1/2 .43 348 150 236 101 376 162 HP-3 Hood 7 1/4 x 8 1/2 .43 581 250 253 109 599 258 TOTAL 550 333 576 ---- REMARKS: r' i I( C�' T ' 3i2 2 fI 1 ROC:215121 NEBB:#3355 Test Date: 01/17/12 Readings By: CH Page: 2 i