HomeMy WebLinkAbout41695 (2) /-1, I
i\JKIiPII B I 1850 N. Central Avenue, Suite #550
f ".' h Alak. j Bl l i-� ►' �;/ Phoenix, Arizona 85004
ENGINEERING, L.L.C. Ph: (602) 393-0201 Fax: (602) 393-0202
June 12,2008
Redden Construction,Inc.
2201.South 7th Avenue Suite 1
Phoenix,Arizona 85007
Attn: Thomas Johns
Re: White Shell Improvement
S.W.C.43`d Ave.&Peoria Ave.ste. 101 &102
Gentlemen:
We understand that you are not going to install the new 1200 amp service entrance section at this time and that the 1200 amp
service will be installed when there is a major tenant for the building.We also understand that there is one tenant in suite 101
in the building and that you wish to feed this tenant's panel from the existing 400 amp service.
The load on Panel 101 is 87 amps at 208 volt,3 phase.This panel is series rated 65/10K.It is safe to feed this panel from the
existing 400 amp service until the service is replaced.
Regards,
pESslonat E-04,4
Kenneth R.Syk ra,P.E. �"r.�`
Electrical Engineer
' KENNETH I CHM! v