Systems Commissioning & Testing, Inc.
16772 W. Bell Rd. Ste 110-432 Surprise,AZ 85374 (520)884-4792
Dustin M. Fielden,President Toll Free: (866)-334-7119 AZ ROC License#081448L-39
Associated Air Balance Council
AABC
MIFF
AABC
MECHANICAL SYSTEM
TEST AND BALANCE REPORT
FOR
PRO CT: LITCHFIELD EASY STORAGE
LOCATION: 5960 N LITCHFIELD RD GLENDALE AZ USA
MECHANICAL ENGINEER: ARDEBILI ENGINEERING
MECHANICAL CONTRACTOR: TRI MEGA MECHANICAL
This is to certify that Systems Commissioning&Testing, Inc., has balanced the systems de-
scribed herein to their optimum performance capabilities. The testing has been performed in
ac-cordance with the standard requirements and procedures of the Associated Air Balance
Council and the results of these tests are herein recorded.
o
Associated Air Balance Council Certification Number: 04-01-63 cP N`asanrn.
d�4
May 30, 2023 `9 .Al,r viitirs;V
9 �
e, :
•2I.0�+ 0
�aUq M. Ptah°�
r
Systems Commissioning & 7"esting, Inc.
16772 W.Bell Rd. Ste 110-432 Surprise,AZ 85374 (520)884-4792 (623)986-2350
Dustin M. Fielden,President Toll Free: (866)-334-7119 AZ ROC License#081448L-39
Associated Air Balance Council
AABC
MOW
AABC
TABLE OF CONTENTS
A.)TITLE PAGE
B.)TABLE OF CONTENTS
C.)NATIONAL PERFORMANCE GUARANTY
D.)GENERAL COMMENTS (BALANCE SUMMARY)
E.)TEST AND BALANCE DATA SHEETS
F.)MECHANICAL DRAWINGS
, , AABC CERTIFIED
Systems
Commissioning 8 TABLE OF CONTENTS
Testing,Inc.
PROJECT: LITCHFIELD EASY STORAGE
1 FCU 1-1/CU 1-1 Split Unit
2 FCU 1-1 SUPPLY Terminal Device
3 FCU 1-2/CU 1-2 Split Unit
4 FCU 1-2 SUPPLY Terminal Device
5 FCU 1-3/CU 1-3 Split Unit
6 FCU 1-3 SUPPLY Terminal Device
7 ECU 2-1/CU 2-1 Split Unit
8 FCU 2-1 SUPPLY Terminal Device
9 FCU 2-2/CU 2-2 Split l nit
10 FCU 2-2 SUPPLY 'Terminal Device
11 FCU 2-3/CU 2-3 Split Unit
12 FCU 2-3 SUPPLY Terminal Device
13 FCU 3-1/CU 3-1 Split Unit
14 FCU 3-1 SUPPLY Terminal Device
15 FCU 3-2/CU 3-2 Split Unit
16 FCU 3-2 SUPPLY Terminal Device
17 FCU 3-3/CU 3-3 Split Unit
18 FCU 3-3 SUPPLY Terminal Device
19 FCU 3-4/CU 3-4 Split Unit
20 FCU 3-4 SUPPLY 'Terminal Device
21 FCU 3-5/CU 3-5 Split Unit
22 FCU 3-5 SUPPLY Terminal Device
23 IU-I/OU-1 Split Unit
24 IU-2/OU-2 Split Unit
25 EFs-1,2.3 Ceiling Fans
r
„,,
K -R : ationa ...
µ . :
K Performance Guaranty = 1
Pursuant to the agreement between - _
SYSTEMS COMMISSIONING & TESTING, INC.
AABC Certified Testing& Balancing Agency
;I:and TRI MEGA MECHANICAL +'
Client '"
:•_ _
" All systems shall be tested and balanced in accordance with the project plans and specifications ':
and to the optimum performance capabilities of the equipment.Testing and balancing shall be done
` - in accordance with the standards published by the Associated Air Balance Council. '
-" ; If the Agency listed above fails to comply with the specifications for any reason other than %
t_,<< termination of business by the AABC agency or equipment malfunction or inadequacy which
i prevents proper balancing of the systems, AABC will investigate and, if warranted, will provide ;
.es supervisory personnel to assist the member Agency to perform work in accordance with AABC = -
i Standards.This supervision will be provided at no additional cost to the building owner.
_-- This Guaranty is valid for one year from the date of submission of a test and balance report,
provided the Agency is a current member of AABC,and may only be invoked in writing by the building "`
owner, architect, or engineer of record. The Guaranty is limited to the terms and conditions as stated
herein. - �‹
-_ ' Project Name
LITCHFIELD EASY STORAGE IAA
./
111 Address
5960 N LITCHFIELD RD GLENDALE AZ USA cr:
;g %V
"i Name of Engineer FAISAL H ELHALIS _ ,-
• `, Engineering Firm ARDEBILI ENGINEERING ,r'
= - Email Address
tri
Address 8100 E INDIAN SCHOOL RD SUITE 205 `;
SCOT0/2023 , AZ 85251
le
ID
05/30/2023 AABC
Date Associated Air -,
:;.: 04-01-63 Balance Council
TBE# e
- 2401 Pennsylvania Ave NW,Ste 330
DUSTIN M. FIELDEN Washington, D.C. 20037 ib
By ----- 202-737-0202•Fax 202-315-0825
AABC Certifiedwww.aabc.com
TBE info@aabc.com• .�
:aErg;
/' ;i'Fir Marc: :; .. : .. ;: ;: .. :; .. :; .' '. .. .II . iIPnlyf: '`�
\ \A i< h\ A `A >t I it A n ri \ xI \ A A x. ". A /
` t •
Systems Commissioning & Testing, Inc.
16772 W. Bell Rd. Ste 110-432 Surprise,AZ 85374 (520) 884-4792 (623)986-2350
Dustin M. Fielden, President Toll Free: (866)-334-7119 AZ ROC License#081448L-39
Associated Air Balance Council
AABC Certified Member
AABC
LITCHFIELD EASY STORAGE
We have completed the testing, adjusting and balancing at the above
referenced project and would like to report that all systems are performing
as specified.
AABC
Associated Air Balance Council
AABC
Certified Member
AABC CERTIFIED
SPLIT UNIT TEST
CSystemsommiss 8
1 Testing, nc.ioning
PROJECT: LITCHFIELD EASY STORAGE DATE: 5/24/2023
MANUFACTURER: 'CARRIER
TYPE: Heat Pump Split Unit MODEL NUMBER (EVAP): IFX4DNF049
SYSTEM: ICU 1-1/CU 1-1 MODEL NUMBER(COND): '25HCE448A600
EOUIPMENT LOCATION: CEILING SERIAL NUMBER(EVAP): 12922F05038
AREA SERVED: BASEMENT SERIAL NUMBER(COND): 14122E11451
REQUIRED FINAL
TOTAL CFM: 1600 1670
OUTSIDE AIR CFM: 210 200(1)
ESP: 0.50 0.22"
DEVICE IN OUT DELTA P
FAN 0.13
FILTER -0.09
REQUIRED FINAL
EVAP MOTOR VOLTAGE: 208/1 487/486/486
EVAPORATIVE MOTOR HP: 0.75 3/4
EVAPORATIVE MOTOR RPM: 3 SPD SPD 2
EVAPORATIVE MOTOR AMPS: 0.0 2.8
COMPRESSOR VOLTAGE: 460 3 487/486/486
COMPRESSOR AMPS: 6.0 3.3/3.4/3.7
CONDENSER AMPS: 0.77 0.66
FAN RPM: I SPD 2
MOTOR SHEAVE: D I R 1 CI D R I V E
FAN SHEAVE:
BELT SIZE(#OF):
CENTER TO CENTER:
NOTES:
TEMPERATURES ENTERING LEAFING (I)OAFA=6"s=0.20 FT2 x 992 AFPM=200 CFM
DRY BULB: 75 55
WET BULB: 64 50
HEATING(DB ONLY): 75 89
OSA DB OSA NA
85 I 74
1
AABC CERTIFIED
... .:Systemssioning 8.
TERMINAL DEVICE SHEET
Commis
Testing,Inc.
PROJECT: LITCHFIELD EASY STORAGE DATE: 5/24/2023
SYSTEM: FCU 1-1
TYPE: SUPPLY
REQUIRED PRELIMINARY FINAL
ROOM# TERMINAL SIZE Ak RDG CFM RDG CFM RDG CFM
BASEMENT 1 12x8 0.66 606 400 692 455 623 410
BASEMENT 2 12x8 0.66 606 400 667 440 643 42
BASEMENT 3 12x8 0.66 606 400 634 420 636 4:1(1
BASEMENT 4 12x8 0.66 606 400 627 415 631 41
TOTAL CFM: [ 1600 1730 1670
NOTES:
•
AABC CERTIFIED
Commiss Systems ioning
SPLIT UNIT TEST
8
Testing,Inc.
PROJECT: LITCHFIELD EASY STORAGE DATE: 5/24/2023
MANUFACTURER: (CARRIER
TYPE: Heat Pump Split Unit MODEL NUMBER (EVAP): (FX4DNF049
SYSTEM: FCU 1-2 CU 1-2 MODEL NUMBER(COND): I25HCI:448A600
EOUIPMENT LOCATION: 1- CEILING SERIAL NUMBER(EVAP): I2922F05025
AREA SERVED: BASEMENT SERIAL NUMBER(COND): 14422E21472
REQUIRED FINAL
TOTAL CFM: 1600 1695
OUTSIDE AIR CFM: 0 0
ESP: 0.50 0.11"
DEVICE IN OUT DELTA P
FAN 0.06
FILTER -0.05 �� J
REQUIRED FINAL
EVAP MOTOR VOLTAGE: 208/1 488/486/486
EVAPORATIVE MOTOR HP: 0.75 3/4
EVAPORATIVE MOTOR RPM:I 3 SPD SPD 2
EVAPORATIVE MOTOR AMPS: 6.0 2.4
COMPRESSOR VOLTAGE: 460/3 488/486/486
COMPRESSOR AMPS: 6.0 3.6/3.8/3.9
CONDENSER AMPS: 0.77 0.67
FAN RPM: I SPD 2
MOTOR SHEAVE: DIRT CT DRIVE
FAN SHEAVE:
BELT SIZE(#OF):
CENTER TO CENTER:
NOTES:
TEMPERATURES ENTERING LEAVING
DRY BULB: 75 5 i
WET BULB: 63 49
HEATING(DB ONLY): 75 II 88
OSADB OSAWB
84 72
AABC CERTIFIED
�,�„systems
Commissioning& TERMINAL DEVICE SHEET
Testing,lnc.
PROJECT: LITCHFIELD EASY STORAGE DATE: 5/24/2023
SYSTEM: I:CI 1-2
TYPE: SUPPLY
REQUIRED PRELIMINARY FINAL
ROOM# TERMINAL SIZE Ak RDG CFM RDG CFM RDG ('FM
BASEMENT I 120 0.66 606 400 669 440 657 4
BASEMENT 2 12x8 0.66 606 400 823 540 636 -120
BASEMENT 3 12x8 0.66 606 400 254 165 629 41
BASEMENT 4 I2x8 0.66 606 400 682 450 645 4)5
TOTAL CFM: 1600 1595 I 695
NOTES:
1
AABC CERTIFIED
System SPLIT UNIT TEST
Commission 8
Testing,Inc.ing
PROJECT: LITCHFIELD EASY STORAGE DATE: 5/24/2023
MANUFACTURER: 'CARRIER
TYPE: Heat Pump Split Unit MODEL NUMBER (EVAP): IFX4DNF049
SYSTEM: I'CU 1-3/CU 1-3 MODEL NUMBER(COND): 125HCE448A600
EOUIPMENT LOCATION: CEILING SERIAL NUMBER(EVAP): [3122F04698
AREA SERVED: BASEMENT SERIAL NUMBER(COND): 14122E11451
REQUIRED FINAL
TOTAL CFM: 1600 1650
OUTSIDE AIR CFM: 0 0
ESP: 0.50 0.16"
DEVICE IN OUT DELTA P
FAN 0.09
FILTER -0.07 I
REQUIRED FINAL
EVAP MOTOR VOLTAGE: I 208,1 486/487/487
EVAPORATIVE MOTOR HP: I 0.75 3/4
EVAPORATIVE MOTOR RPM: 3 SPD SPD 2
EVAPORATIVE MOTOR AMPS: l 6.0 2.6
COMPRESSOR VOLTAGE: 460 ; 486/487/487
COMPRESSOR AMPS: 6.0 3.5/3.9/4.0
CONDENSER AMPS: 0.77 0.65
FAN RPM: I SPD 2
MOTOR SHEAVE: I)I R I C I I)R I V E
FAN SHEAVE:
BELT SIZE(#OF):
CENTER TO CENTER:
NOTES:
TEMPERATURES EN"TERING LEAN INC
DRY BULB: 74 54
WET BULB: 61 48
HEATING(DB ONLY): 74 90
OSA DB OSA WB
I 84 1 73
•
. . AABC CERTIFIED
TERMINAL DEVICE SHEET
CommSystems issioning&
��Testing,Inc.
PROJECT: LITCHFIELD EASY STORAGE DATE: 5/24/2023
SYSTEM: FCU 1-3
TYPE: SUPPLY
REQUIRED PRELIMINARY FINAL
ROOM# TERMINAL SIZE Ak RDG CFM RDG CFM RDG CFM
BASEMENT 1 12x8 0.66 606 400 589 390 589 390
BASEMENT 2 12x8 0.66 606 400 645 425 645 425
BASEMENT 3 12x8 0.66 606 400 651 430 651 .1;ii
BASEMENT 4 12x8 0.66 606 400 611 405 611 4115
TOTAL CFM: 1600 1650 1650 J
NOTES:
6
•
AABC CERTIFIED
-�Systems
Commissioning 8 SPLIT UNIT TEST
Testing,Inc.
PROJECT: LITCHFIELD EASY STORAGE DATE: 5/26/2023
MANUFACTURER: 'CARRIER
TYPE: Heat Pump Split Unit MODEL NUMBER (EVAP): IFXDNF049
SYSTEM: FCU 2-1 CU 2-1 MODEL NUMBER(COND): 125HCW448A600
EOUIPMENT LOCATION: ROOF SERIAL NUMBER(EVAP): 12922F05051
AREA SERVED: 1ST FLOOR SERIAL NUMBER(COND): 14122E11458
REQUIRED FINAL
TOTAL CFM: 1200 1240
OUTSIDE AIR CFM: 110 105(1)
ESP: 0.50 0.14"
DEVICE IN OUT DELTA P
FAN 0.08 I. I
FILTER -0.06
REQUIRED FINAL
EVAP MOTOR VOLTAGE: 208/1 487/486/488
EVAPORATIVE MOTOR HP: 0.75 3/4
EVAPORATIVE MOTOR RPM: 3 SPD SPD 2
EVAPORATIVE MOTOR AMPS: 6.0 2.8
COMPRESSOR VOLTAGE: 460 3 487/486/488
COMPRESSOR AMPS: 6.0 3.4/3.7/3.6
CONDENSER AMPS: 0.77 0.69
FAN RPM: SPD 2
MOTOR SHEAVE: I)I R I L I D R I VI
FAN SHEAVE: I
BELT SIZE(#OF):
CENTER TO CENTER:
NOTES:
TEMPERATURES ENTERING LEAVING (1)OAFA=6"e=0.20 FT2 x 512 FPM=105 CFM
DRY BULB: 76 52
WET BULB: 62 47
HEATING(DB ONLY): 72 89
OSA DB OSA RB
84 72
7
•
AABC CERTIFIED
C,Systems g TERMINAL DEVICE SHEET
Commissionin &
ow
Testing,Inc.
PROJECT: LITCHFIELD EASY STORAGE DATE: 5/24/2023
SYSTEM: FCU 2-I
TYPE: SUPPLY
REQUIRED PRELIMINARY FINAL
ROOM# TERMINAL SIZE Ak RDG CFM RDG CFM RDG CFM
1ST FLOOR 1 12x8 0.66 606 400 639 420 639 420
1ST FLOOR 2 12x8 0.66 606 400 624 410 624 410
1ST FLOOR 3 12x8 0.66 606 400 622 410 622 410
TOTAL CFM: 1200 1240 1240
NOTES:
8
•
AABC CERTIFIED
Systems Commi SPLIT UNIT TEST
s &
Testing,Inc.sioning
PROJECT: LITCHFIELD EASY STORAGE DATE: 5/26/2023
MANUFACTURER: 'CARRIER
TYPE: Heat Pump Split Unit MODEL NUMBER (EVAP): IFXDNF037
SYSTEM: FCU 2-2/CU 2-2 MODEL NUMBER(COND): I25HCE436A610
EOUIPMENT LOCATION: ROOF SERIAL NUMBER(EVAP): I0522F25571
AREA SERVED: 1ST FLOOR SERIAL NUMBER(COND): 1922E03383
REQUIRED FINAL
TOTAL CFM: 1200 1275
OUTSIDE AIR CFM: 75 75(1)
ESP: 0.50 0.18"
DEVICE IN OUT DELTA P
FAN 0.1
FILTER I -0.08 I I
REQUIRED FINAL
EVAP MOTOR VOLTAGE: 208/1 I 489/484/486
EVAPORATIVE MOTOR HP: 0.75 3/4
EVAPORATIVE MOTOR RPM: 3 SPD SPD 2
EVAPORATIVE MOTOR AMPS: 4.1 2.8
COMPRESSOR VOLTAGE: 460/3 489/484 486
COMPRESSOR AMPS: 3.85 2.3/1.8/2.0
CONDENSER AMPS: 0.60 0.55
FAN RPM: SPD 2
MOTOR SHEAVE: DIRECT DRIVE
FAN SHEAVE:
BELT SIZE(#OF): I
CENTER TO CENTER:
NOTES:
TEMPERATURES ENTERING LEANING (1)OAFA=6"0=0.20 FT2 x 378 AFPM=75 CFM
DRY BULB: 75 ;5
WET BULB: 61 49
HEATING(DB ONLY): L. 75 88
OSA DB OSA WB
84 I 73
9
AABC CERTIFIED
C,_Systems TERMINAL DEVICE SHEET
Commissioning&
Testing,Inc.
PROJECT: LITCHFIELD EASY STORAGE DATE: 5/24/2023
SYSTEM: FCU 2-2
TYPE: SUPPLY
REQUIRED PRELIMINARY FINAL
ROOM# TERMINAL SIZE Ak RDG CFM RDG CFM RDG CFM
LOBBY I 12x8 0.66 454 300 185 125 488 320
LOBBY 2 12x8 0.66 454 300 163 105 475 3 I
RR 3 4 1.0 50 90
RR 4 4 1.0 50 65 >
LOBBY 5 12x8 0.66 454 300 750 495 479 31
BREAK RM 6 8 1.0 200 245 21
TOTAL CFM: 1200 1125 1275
NOTES:
10
AABC CERTIFIED
C Systems SPLIT UNIT TEST
Commissionin &
Testing,Inc. g
PROJECT: LITCHFIELD EASY STORAGE DATE: 5/26/2023
MANUFACTURER: 'CARRIER
TYPE: Heat Pump Split Unit MODEL NUMBER (EVAP): IFXDNF037
SYSTEM: FCU 2-3 CU 2-3 MODEL NUMBER(COND): I25HCE436A610
EOUIPMENT LOCATION: ROOF SERIAL NUMBER(EVAP): '0522F25013
AREA SERVED: 2ND FLOOR SERIAL NUMBER(COND): 1922E03381
REQUIRED FINAL
TOTAL CFM: 1600 1685
OUTSIDE AIR CFM: 0 0
ESP: 0.50 0.13"
DEVICE IN OUT DELTA P
FAN 0.07 I
Iiimmutri -0.06 I I
REQUIRE!) FINAL
EVAP MOTOR VOLTAGE: 208/1 486/487/488
EVAPORATIVE MOTOR HP: 0.75 3/4
EVAPORATIVE MOTOR RPM: L 3 SPI) SPD 2
EVAPORATIVE MOTOR AMPS: 4.1 2.1
COMPRESSOR VOLTAGE: 460 3 486/487/488
COMPRESSOR AMPS: 3.85 1.9/1.7'2.1
CONDENSER AMPS: 0.60 0.47
FAN RPM: I SPD 2
MOTOR SHEAVE: I)0/I CT DRIVE
FAN SHEAVE:
BELT SIZE(#OF):
CENTER TO CENTER:
NOTES:
TEMPERATURES ENTERING LEAVING
DRY BULB: 76 54
WET BULB: 63 49
HEATING(DB ONLY): 76 90
OSA DB OSA WB
84 I 72
II
AABC CERTIFIED
--.. SystCommissems Testing,Inc.ioning 8
TERMINAL DEVICE SHEET
PROJECT: LITCHFIELD EASY STORAGE DATE: 5/24/2023
SYSTEM: FCU 2-3
TYPE: SUPPLY
REQUIRED PRELIMINARY FINAL
ROOM# TERMINAL SIZE Ak RDG CFM RDG CFM RDG CFM
1ST FLOOR 1 12x8 0.66 606 400 448 295 617 410
i
1ST FLOOR 2 12x8 0.66 606 400 687 455 625 415
1ST FLOOR 3 12x8 0.66 606 400 786 520 664 440
1ST FLOOR 4 12x8 0.66 606 400 627 415 635 420
TOTAL CFM: 1600 1685 1685
NOTES:
12
•
AABC CERTIFIED
systes SPLIT UNIT TEST
ommissioning m &Testing,tnc.
PROJECT: LITCHFIELD EASY STORAGE DATE: 5/26/2023
MANUFACTURER: [CARRIER
TYPE: Heat Pump Split Unit MODEL NUMBER (EVAP): (FX4DNF037
SYSTEM: FCU 3-1/CU 3-1 n1ODEL NUMBER(COND): 125 HCE436A610
EOUIPMENT LOCATION: ROOF SERIAL NUMBER(EVAP): 10522E25078
AREA SERVED: 2ND FLOOR SERIAL NUMBER(COND): 1922E 18100
REQUIRED FINAL
TOTAL CFM: 1200 1225
OUTSIDE AIR CFM: 75 80(1)
ESP: 0.50 0.09"
DEVICE 1N OUT DELTAP
FAN 0.05
IFILTER -0.04
REQUIRED FINAL
EVAP MOTOR VOLTAGE: ( 208/1 484/486/486
EVAPORATIVE MOTOR HP: 0.50 1/2
EVAPORATIVE MOTOR RPM: 3 SPD SPD 2
EVAPORATIVE MOTOR AMPS: 4.1 j 2.0
COMPRESSOR VOLTAGE: 460/3 484/486%486
COMPRESSOR AMPS: 3.85 190
CONDENSER AMPS: 0.60 0.45
FAN RPM: SPD 2
MOTOR SHEAVE: DIRECT DRIVE
FAN SHEAVE:
BELT SIZE(#OF):
CENTER TO CENTER:
NOTES:
TEM PERATURES ENTERING LEAVING (I)OAFA=6"e=0.20 FT2 x 404 AFPM=80 CFM
DRY BULB: 75 r 55
WET BULB: 6; 3tt
HEATING(DB ONLY): 75 N8
OSA DB OSA WB
84 ( 72
13
AABC CERTIFIED
Systems
mmiss 8,ionin TERMINAL DEVICE SHEET
o
Testing,Inc. g
PROJECT: LITCHFIELD EASY STORAGE DATE: 5/24/2023
SYSTEM: FCU 3-1
TYPE: SUPPLY
REQUIRED PRELIMINARY FINAL
ROOM# TERMINAL SIZE Ak RDG CFM RDG CFM RDG CFM
2ND FLOOR 1 12x8 0.66 606 400 593 390 593 390
2ND FLOOR 2 12x8 0.66 606 400 652 430 652 430
2ND FLOOR 3 12x8 0.66 606 400 613 405 613 41)5
TOTAL CFM: 1200 1225 1225
NOTES:
14
•
AABC CERTIFIED
C,Systems SPLIT UNIT TEST
Commissionin &
Testing,Inc. g
PROJECT: LITCHFIELD EASY STORAGE DATE: 526/2023
MANUFACTURER: 'CARRIER
TYPE: Heat Pump Split Unit MODEL NUMBER (EVAP): IFX4DNF049
SYSTEM: FCU 3-2/CU 3-2 MODEL NUMBER(COND): I25HCE448A600
EOUIPMENT LOCATION: ROOF SERIAL NUMBER(EVAP): 12522E01843
AREA SERVED: 2ND FLOOR SERIAL NUMBER(COND): 14122E 11452
REQUIRED FINAL
TOTAL CFM: 1600 1690
OUTSIDE AIR CFM: 75 80(1) • I
ESP: 0.50 0.18"
DEVICE IN OUT DELTA P
FAN 0.1
FILTER -0.08
REQUIRED FINAL
EVAP MOTOR VOLTAGE: 208/1 489/486/488
EVAPORATIVE MOTOR HP: I 0.75 3/4
EVAPORATIVE MOTOR RPM: 3 SPD SPD 2
EVAPORATIVE MOTOR AMPS: 6.0 2.9
COMPRESSOR VOLTAGE: 460/3 489/486/488
COMPRESSOR AMPS: 6.0 2.9/3.3/3.0
CONDENSER AMPS: 0.77 0.66
FAN RPM: 1 SPD 2
MOTOR SHEAVE: DIRECT DRIVE
FAN SHEAVE:
BELT SIZE(#OF):
CENTER TO CENTER:
NOTES:
TEMPERATURES ENTERING LEAVING (I)OAFA=6"e=0.20 FT2 x 414 AFPM=80 CFM
DRY BULB: 76 54
WET BULB: 6 I 50
HEATING(DB ONLY): I 70 89
OSA DB OSA WB
84 I 74
15
AABC CERTIFIED
Systems(-CommsmfltnY& TERMINAL DEVICE SHEET
▪ Testing.Inc.
PROJECT: LITCHFIELD EASY STORAGE DATE: 5/24/2023
SYSTEM: FCU 3-2
TYPE: SUPPLY
REQUIRED PRELIMINARY FINAL
ROOM# TERMINAL SIZE Ak RDG CFM RDG CFM RDG ('FV1
2ND FLOOR 1 12x8 0.66 606 400 622 410 634 42(
2ND FLOOR 2 12x8 0.66 606 400 605 400 612 40;
2ND FLOOR 3 12x8 0.66 606 400 670 440 664 4
2ND FLOOR 4 12x8 0.66 606 400 674 445 653 410
TOTAL CFM: 1600 1695 169O
NOTES:
I t,
•
. . AABC CERrIFlED
Systems SPLIT UNIT TEST
"' Commio 8
Testing iss,I ncning.
PROJECT: LITCHFIELD EASY STORAGE DATE: 5/26/2023
MANUFACTURER: (CARRIER
TYPE: Heat Pump Split Unit MODEL NUMBER (EVAP): IFX4DNF049
SYSTEM: FCU 3-3/CU 3-3 MODEL NUMBER(COND): 125HCE448A600
EOUIPMENT LOCATION: ROOF SERIAL NUMBER(EVAP): I2922F05046
AREA SERVED: 2ND FLOOR SERIAL NUMBER(COND): 14422E21705
REQUIRED FINAL
TOTAL CFM: 1600 1670
OUTSIDE AIR CFM: 75 80(1)
ESP: 0.50 0.18"
DEVICE IN OUT DELTA P
FAN 0.11 I I
FILTER -0.7 J
REQUIRED FINAL
EVAP MOTOR VOLTAGE: 208/1 488/489/488
EVAPORATIVE MOTOR HP: 0.75 3/4
EVAPORATIVE MOTOR RPM: 3 SPD SPD 2
EVAPORATIVE MOTOR AMPS: 6.0 3.1
COMPRESSOR VOLTAGE: 460/3 J 488/489'488
COMPRESSOR AMPS: 6.0 2.9/3.3/3.1
CONDENSER AMPS: 0.77 0.65
FAN RPM: ( SPD 2
MOTOR SHEAVE: DIRECT DRIVE
FAN SHEAVE:
BELT SIZE(#OF):
CENTER TO CENTER:
NOTES:
TEMPERATURES ENI'ER1NG LEAN INC (I)OAFA=6"0=0.20FT2x397 Al-PM=80CFM
DRY BULB: 76 53
WET BULB: 6; 49
HEATING(DB ONLY): 76 88
OSA DE OSA WR
84 I 74
17
•
. , AABC CERTIFIED
Systems'-Commissioning& TERMINAL DEVICE SHEET
▪ Testing,Inc.
PROJECT: LITCHFIELD EASY STORAGE DATE: 5 24 2023
SYSTEM: I'Cl: 3-3
TYPE: SI IPPI V
REQUIRED PRELIMINARY FINAL
ROOM# TERMINAL SIZE Alt RDG CFM RDG CFM RDC CFM
2ND FLOOR 1 12x8 0.66 606 400 612 405 623 410
2ND FLOOR 2 12x8 0.66 606 400 598 395 6C2 41)u
2ND FLOOR 3 12x8 0.66 606 400 639 420 641 425
2ND FLOOR 4 12x8 0.66 606 400 688 455 661 415
TOTAL CFM: 1600 1675 167o
NOTES:
I�
AABC CERTIFIED
Systems SPLIT UNIT TEST
Commissioning 8
Testing,Inc.
PROJECT: LITCHFIELD EASY STORAGE DATE: 5/26/2023
MANUFACTURER: 1ARRIER
TYPE: Heat Pump Split Unit MODEL NUMBER (EVAPI: IFX4DNF049
SYSTEM: FCU 3-4/CU 3-4 MODEL NUMBER(COND): (25HCE448A600
EOUIPMENT LOCATION: ROOF SERIAL NUMBER(EVAP): I2522F01861
AREA SERVED: 2ND FLOOR SERIAL NUMBER(COND): 14422E21468
REQUIRED FINAL
TOTAL CFM: 1600 1615
OUTSIDE AIR CFM: 75 75(1)
ESP: 0.50 0.1 5"
1)E\ ICE IN OUT DELTA P
FAN 0.09
FILTER -0.06
REQUIRED FINAL
EVAP MOTOR VOLTAGE: 208'1 487/488/485
EVAPORATIVE MOTOR HP: 0.75 3/4
EVAPORATIVE MOTOR RPM: 3 SPD SPD 2
EVAPORATIVE MOTOR AMPS: 6.0 3.2
COMPRESSOR VOLTAGE: 460/3 487/488 485
COMPRESSOR AMPS: 6.0 2.8/3.1
CONDENSER AMPS: 0.77 0.65
FAN RPM: I SPD 2
MOTOR SHEAVE: DIRECT DRIVE
FAN SHEAVE:
BELT SIZE(#OF):
CENTER TO CENTER:
NOTES:
TEMPERATURES EN l F:12ING LEAVING (1)OAFA=6"e=0.20 FT2 x 389 AFPM=75 CFM
DRY BULB: 77 52
WET BULB: 62 49
HEATING(DB ONLY): 77 88
OSA DB OSA RB
I 84 I 74
19
AABC CERTIFIED
` Systems Testing,Inc. g miss &ionin TERMINAL DEVICE SHEET
PROJECT: LITCHFIELD EASY STORAGE DATE: 5/24/2023
SYSTEM: FCU 3-4
TYPE: SUPPLY
REQUIRED PRELIMINARY FINAL
ROOM# TERMINAL SIZE Ak RDG CFM RDG CFM RDG CFM
2ND FLOOR 1 12x8 0.66 606 400 623 410 623 410
2ND FLOOR 2 12x8 0.66 606 400 630 415 630 41
2ND FLOOR 3 12x8 0.66 606 400 589 390 589 ,01)
2ND FLOOR 4 12x8 0.66 606 400 602 400 602 406
TOTAL CFM: 1600 1615 1615
NOTES:
'u
•
AABC CERTIFIED
Csmtemnl
SPLIT UNIT TEST
Coioning 8
Testing,Inc.
PROJECT: LITCHFIELD EASY STORAGE DATE: 5-'26/2023
MANUFACTURER: CARRIER
TYPE: Heat Pump Split Unit MODEL NUMBER (EVAP): (FX4DNF049
SYSTEM: FCU 3-5/CU 3-5 MODEL NUMBER(COND): I25HCE448A600
EOUIPMENT LOCATION: ROOF SERIAL NUMBER(EVAP): I3022F13803
AREA SERVED: 2ND FLOOR SERIAL NUMBER(COND): 14122E11448
REQUIRED FINAL
TOTAL CFM: 1600 1645
OUTSIDE AIR CFM: 75 80(1)
ESP: 0.50 0.19"
DEVICE IN OUT DELTA P
FAN 0.1 I
FILTER -0.09
REQUIRED FINAL
EVAP MOTOR VOLTAGE: 208/1 487/486/488
EVAPORATIVE MOTOR HP: 0.75 3/4
EVAPORATIVE MOTOR RPM: 3 SPD SPD 2
EVAPORATIVE MOTOR AMPS: 6.0 3.0
COMPRESSOR VOLTAGE: 460/3 487/486i488
COMPRESSOR AMPS: 6.0 2.8/3.0/3.1
CONDENSER AMPS: 0.77 0.64
FAN RPM: SPD 2
MOTOR SHEAVE: 1)IRI 11)RIVI
FAN SHEAVE: I
BELT SIZE(#OF):
CENTER TO CENTER:
NOTES:
TEMPERATURES ENTERING LEAVING (I)OAFA=6"e=0.20 FT2 x 401 AFPM=80 CFM
DRY BULB: 76 52
WET BULB: (U 46
HEATING(DB ONLY): 76 90
OSA DB OSA WB
84 I 74
21
AABC CERTIFIED
Systems ioning& TERMINAL DEVICE SHEET
Testing,Inc.
PROJECT: LITCHFIELD EASY STORAGE DATE: 5/24/2023
SYSTEM: FCU 3-5
TYPE: SUPPLY"
REQUIRED PRELIMINARY FINAL
ROOM# TERMINAL SIZE Ak RDG CFM RDG CFM RDG CFM
2ND FLOOR 1 12x8 0.66 454 300 495 325 487 320
2ND FLOOR 2 12x8 0.66 606 400 639 420 618 li).;
2ND FLOOR 3 12x8 0.66 378 250 404 265 388 2 5
2ND FLOOR 4 12x8 0.66 606 400 585 385 611 405
2ND FLOOR 5 12x8 0.66 378 250 523 345 398 260
TOTAL CFM: 1600 1740 1645 7
NOTES:
22
AABC CERTIFIED
Systems SPLIT UNIT TEST
Commissioning
Testing,Inc.
PROJECT: LITCHFIELD EASY STORAGE DATE: 5 26/2023
MANUFACTURER: JLENNOX
TYPE: MODEL NUMBER (EVAP): 140MAHBQ18XA3
SYSTEM: IU-l/OU-1 MODEL NUMBER(COND): 138MARBQ18AA301
EOUIPMENT LOCATION: ROOF SERIAL NUMBER(EVAP): 1341 V 14064
AREA SERVED: MECH ROOM SERIAL NUMBER(COND): )0822V33579
REQUIRED FINAL
TOTAL CFM: 442 -442
OUTSIDE AIR CFM: N/A N/A
ESP: N/A N/A
DEVICE IN UUT DELTA P
FAN
FILTER I II I
REQUIRED FINAL
EVAP MOTOR VOLTAGE: 208/1 210/1
EVAPORATIVE MOTOR HP: NOT LISTED NOT LISTED
EVAPORATIVE MOTOR RPM: VARIABLE USER CONTROLLED
EVAPORATIVE MOTOR AMPS: 3.I) 1.8
COMPRESSOR VOLTAGE: 20 I 210
COMPRESSOR AMPS: I 7.8
CONDENSER AMPS: I 0 0.70
FAN RPM: USER CONTROLLED
MOTOR SHEAVE: DIRECT DRIVE
FAN SHEAVE:
BELT SIZE(#OF):
CENTER TO CENTER: 1
NOTES:
TEMPERATURES ENTERING LEAVING
DRY BULB: ( 70 54
WET BULB: 53 49
HEATING(DB ONLY): N.A N/A
Us t DB OSA WB
NA I_ N A
AABC CERTIFIED
Systems SPLIT UNIT TEST
Commissioning 8
Testing,Inc.
PROJECT: LITCHFIELD EASY STORAGE DATE: 5/26/2023
MANUFACTURER: 'LENNOX
TYPE: MODEL NUMBER (EVAP): (MWMC018S4
SYSTEM: MODEL NUMBER(COND): IMPC018S4S
EOUIPMENT LOCATION: ROOF SERIAL NUMBER(EVAP): IS6922H01080
AREA SERVED: ELEVATOR ROOM SERIAL NUMBER(COND): IS6922F08155
REQUIRED FINAL
TOTAL CFM: 600 +/-600
OUTSIDE AIR CFM: N/A N/A
ESP: N/A N/A
DEVICE IN OUT I)EI.TA P
FAN
FILTER _ I
REQUIRED FINAL
EVAP MOTOR VOLTAGE: 208/1 209/I
EVAPORATIVE MOTOR HP: NOT LISTED NOT LISTED
EVAPORATIVE MOTOR RPM: VARIABLE I( USER CONTROLLED
EVAPORATIVE MOTOR AMPS: 2.0
COMPRESSOR VOLTAGE: ?ilx I 209/I
COMPRESSOR AMPS: 1;.(1 6.9
CONDENSER AMPS: 0.44 0.44
FAN RPM: USER CONTROLLED
MOTOR SHEAVE: DIRECT DRIVE
FAN SHEAVE:
BELT SIZE(#OFI:
CENTER TO CENTER:
NOTES:
TEMPERATURES EN I'ERING LEAVING
DRY BULB: 70 52
WET BULB: 53 47
HEATING(DB ONLY): I N A N/A
OSA DB OSA WB
N/A N/A
24
AABC CERTIFIED
e Systems
Commissioning& CEILING MOUNTED EXHAUST FANS
Testing,Inc.
PROJECT:LITCHFIELD EASY STORAGE DATE: 2023-05-24T00:00:00
FAN# MODEL# '
ROOM SERVED
MANUFACTURER SERIAL# CFM HP VOLTS AMPS RPM*
EF-1 SP-A90 RR REQUIRED 75 15W 120/1 0.4 1 SPD
GREENHECK 20461585 ACTUAL 80 15W 113/I 0.17 HIGH
EF-2 SP-A90 REQUIRED 75 15W 120/1 0.4 1 SPD
RR
GREENHECK 20461603 ACTUAL 80 15W 1121 0.17 HIGH
EF-3 SP-A90 JAN REQUIRED 75 15W 120 1 0.4 1 SPD
GREENHECK 20461402 ACTUAL 75 15W 112/1 0.17 HIGH
*The fan rpm is the same as the motor rpm since the fan is direct drive.
**The static pressures for these fans are not accessible.
NOTES
25