HomeMy WebLinkAbout00000 (10) r Systems Commissioning & Testing, Inc. 16772 W. Bell Rd. Ste 110-432 Surprise,AZ 85374 (520)884-4792 Dustin M. Fielden,President Toll Free: (866)-334-7119 AZ ROC License#081448L-39 Associated Air Balance Council AABC MIFF AABC MECHANICAL SYSTEM TEST AND BALANCE REPORT FOR PRO CT: LITCHFIELD EASY STORAGE LOCATION: 5960 N LITCHFIELD RD GLENDALE AZ USA MECHANICAL ENGINEER: ARDEBILI ENGINEERING MECHANICAL CONTRACTOR: TRI MEGA MECHANICAL This is to certify that Systems Commissioning&Testing, Inc., has balanced the systems de- scribed herein to their optimum performance capabilities. The testing has been performed in ac-cordance with the standard requirements and procedures of the Associated Air Balance Council and the results of these tests are herein recorded. o Associated Air Balance Council Certification Number: 04-01-63 cP N`asanrn. d�4 May 30, 2023 `9 .Al,r viitirs;V 9 � e, : •2I.0�+ 0 �aUq M. Ptah°� r Systems Commissioning & 7"esting, Inc. 16772 W.Bell Rd. Ste 110-432 Surprise,AZ 85374 (520)884-4792 (623)986-2350 Dustin M. Fielden,President Toll Free: (866)-334-7119 AZ ROC License#081448L-39 Associated Air Balance Council AABC MOW AABC TABLE OF CONTENTS A.)TITLE PAGE B.)TABLE OF CONTENTS C.)NATIONAL PERFORMANCE GUARANTY D.)GENERAL COMMENTS (BALANCE SUMMARY) E.)TEST AND BALANCE DATA SHEETS F.)MECHANICAL DRAWINGS , , AABC CERTIFIED Systems Commissioning 8 TABLE OF CONTENTS Testing,Inc. PROJECT: LITCHFIELD EASY STORAGE 1 FCU 1-1/CU 1-1 Split Unit 2 FCU 1-1 SUPPLY Terminal Device 3 FCU 1-2/CU 1-2 Split Unit 4 FCU 1-2 SUPPLY Terminal Device 5 FCU 1-3/CU 1-3 Split Unit 6 FCU 1-3 SUPPLY Terminal Device 7 ECU 2-1/CU 2-1 Split Unit 8 FCU 2-1 SUPPLY Terminal Device 9 FCU 2-2/CU 2-2 Split l nit 10 FCU 2-2 SUPPLY 'Terminal Device 11 FCU 2-3/CU 2-3 Split Unit 12 FCU 2-3 SUPPLY Terminal Device 13 FCU 3-1/CU 3-1 Split Unit 14 FCU 3-1 SUPPLY Terminal Device 15 FCU 3-2/CU 3-2 Split Unit 16 FCU 3-2 SUPPLY Terminal Device 17 FCU 3-3/CU 3-3 Split Unit 18 FCU 3-3 SUPPLY Terminal Device 19 FCU 3-4/CU 3-4 Split Unit 20 FCU 3-4 SUPPLY 'Terminal Device 21 FCU 3-5/CU 3-5 Split Unit 22 FCU 3-5 SUPPLY Terminal Device 23 IU-I/OU-1 Split Unit 24 IU-2/OU-2 Split Unit 25 EFs-1,2.3 Ceiling Fans r „,, K -R : ationa ... µ . : K Performance Guaranty = 1 Pursuant to the agreement between - _ SYSTEMS COMMISSIONING & TESTING, INC. AABC Certified Testing& Balancing Agency ;I:and TRI MEGA MECHANICAL +' Client '" :•_ _ " All systems shall be tested and balanced in accordance with the project plans and specifications ': and to the optimum performance capabilities of the equipment.Testing and balancing shall be done ` - in accordance with the standards published by the Associated Air Balance Council. ' -" ; If the Agency listed above fails to comply with the specifications for any reason other than % t_,<< termination of business by the AABC agency or equipment malfunction or inadequacy which i prevents proper balancing of the systems, AABC will investigate and, if warranted, will provide ; .es supervisory personnel to assist the member Agency to perform work in accordance with AABC = - i Standards.This supervision will be provided at no additional cost to the building owner. _-- This Guaranty is valid for one year from the date of submission of a test and balance report, provided the Agency is a current member of AABC,and may only be invoked in writing by the building "` owner, architect, or engineer of record. The Guaranty is limited to the terms and conditions as stated herein. - �‹ -_ ' Project Name LITCHFIELD EASY STORAGE IAA ./ 111 Address 5960 N LITCHFIELD RD GLENDALE AZ USA cr: ;g %V "i Name of Engineer FAISAL H ELHALIS _ ,- • `, Engineering Firm ARDEBILI ENGINEERING ,r' = - Email Address tri Address 8100 E INDIAN SCHOOL RD SUITE 205 `; SCOT0/2023 , AZ 85251 le ID 05/30/2023 AABC Date Associated Air -, :;.: 04-01-63 Balance Council TBE# e - 2401 Pennsylvania Ave NW,Ste 330 DUSTIN M. FIELDEN Washington, D.C. 20037 ib By ----- 202-737-0202•Fax 202-315-0825 AABC Certifiedwww.aabc.com TBE info@aabc.com• .� :aErg; /' ;i'Fir Marc: :; .. : .. ;: ;: .. :; .. :; .' '. .. .II . iIPnlyf: '`� \ \A i< h\ A `A >t I it A n ri \ xI \ A A x. ". A / ` t • Systems Commissioning & Testing, Inc. 16772 W. Bell Rd. Ste 110-432 Surprise,AZ 85374 (520) 884-4792 (623)986-2350 Dustin M. Fielden, President Toll Free: (866)-334-7119 AZ ROC License#081448L-39 Associated Air Balance Council AABC Certified Member AABC LITCHFIELD EASY STORAGE We have completed the testing, adjusting and balancing at the above referenced project and would like to report that all systems are performing as specified. AABC Associated Air Balance Council AABC Certified Member AABC CERTIFIED SPLIT UNIT TEST CSystemsommiss 8 1 Testing, nc.ioning PROJECT: LITCHFIELD EASY STORAGE DATE: 5/24/2023 MANUFACTURER: 'CARRIER TYPE: Heat Pump Split Unit MODEL NUMBER (EVAP): IFX4DNF049 SYSTEM: ICU 1-1/CU 1-1 MODEL NUMBER(COND): '25HCE448A600 EOUIPMENT LOCATION: CEILING SERIAL NUMBER(EVAP): 12922F05038 AREA SERVED: BASEMENT SERIAL NUMBER(COND): 14122E11451 REQUIRED FINAL TOTAL CFM: 1600 1670 OUTSIDE AIR CFM: 210 200(1) ESP: 0.50 0.22" DEVICE IN OUT DELTA P FAN 0.13 FILTER -0.09 REQUIRED FINAL EVAP MOTOR VOLTAGE: 208/1 487/486/486 EVAPORATIVE MOTOR HP: 0.75 3/4 EVAPORATIVE MOTOR RPM: 3 SPD SPD 2 EVAPORATIVE MOTOR AMPS: 0.0 2.8 COMPRESSOR VOLTAGE: 460 3 487/486/486 COMPRESSOR AMPS: 6.0 3.3/3.4/3.7 CONDENSER AMPS: 0.77 0.66 FAN RPM: I SPD 2 MOTOR SHEAVE: D I R 1 CI D R I V E FAN SHEAVE: BELT SIZE(#OF): CENTER TO CENTER: NOTES: TEMPERATURES ENTERING LEAFING (I)OAFA=6"s=0.20 FT2 x 992 AFPM=200 CFM DRY BULB: 75 55 WET BULB: 64 50 HEATING(DB ONLY): 75 89 OSA DB OSA NA 85 I 74 1 AABC CERTIFIED ... .:Systemssioning 8. TERMINAL DEVICE SHEET Commis Testing,Inc. PROJECT: LITCHFIELD EASY STORAGE DATE: 5/24/2023 SYSTEM: FCU 1-1 TYPE: SUPPLY REQUIRED PRELIMINARY FINAL ROOM# TERMINAL SIZE Ak RDG CFM RDG CFM RDG CFM BASEMENT 1 12x8 0.66 606 400 692 455 623 410 BASEMENT 2 12x8 0.66 606 400 667 440 643 42 BASEMENT 3 12x8 0.66 606 400 634 420 636 4:1(1 BASEMENT 4 12x8 0.66 606 400 627 415 631 41 TOTAL CFM: [ 1600 1730 1670 NOTES: • AABC CERTIFIED Commiss Systems ioning SPLIT UNIT TEST 8 Testing,Inc. PROJECT: LITCHFIELD EASY STORAGE DATE: 5/24/2023 MANUFACTURER: (CARRIER TYPE: Heat Pump Split Unit MODEL NUMBER (EVAP): (FX4DNF049 SYSTEM: FCU 1-2 CU 1-2 MODEL NUMBER(COND): I25HCI:448A600 EOUIPMENT LOCATION: 1- CEILING SERIAL NUMBER(EVAP): I2922F05025 AREA SERVED: BASEMENT SERIAL NUMBER(COND): 14422E21472 REQUIRED FINAL TOTAL CFM: 1600 1695 OUTSIDE AIR CFM: 0 0 ESP: 0.50 0.11" DEVICE IN OUT DELTA P FAN 0.06 FILTER -0.05 �� J REQUIRED FINAL EVAP MOTOR VOLTAGE: 208/1 488/486/486 EVAPORATIVE MOTOR HP: 0.75 3/4 EVAPORATIVE MOTOR RPM:I 3 SPD SPD 2 EVAPORATIVE MOTOR AMPS: 6.0 2.4 COMPRESSOR VOLTAGE: 460/3 488/486/486 COMPRESSOR AMPS: 6.0 3.6/3.8/3.9 CONDENSER AMPS: 0.77 0.67 FAN RPM: I SPD 2 MOTOR SHEAVE: DIRT CT DRIVE FAN SHEAVE: BELT SIZE(#OF): CENTER TO CENTER: NOTES: TEMPERATURES ENTERING LEAVING DRY BULB: 75 5 i WET BULB: 63 49 HEATING(DB ONLY): 75 II 88 OSADB OSAWB 84 72 AABC CERTIFIED �,�„systems Commissioning& TERMINAL DEVICE SHEET Testing,lnc. PROJECT: LITCHFIELD EASY STORAGE DATE: 5/24/2023 SYSTEM: I:CI 1-2 TYPE: SUPPLY REQUIRED PRELIMINARY FINAL ROOM# TERMINAL SIZE Ak RDG CFM RDG CFM RDG ('FM BASEMENT I 120 0.66 606 400 669 440 657 4 BASEMENT 2 12x8 0.66 606 400 823 540 636 -120 BASEMENT 3 12x8 0.66 606 400 254 165 629 41 BASEMENT 4 I2x8 0.66 606 400 682 450 645 4)5 TOTAL CFM: 1600 1595 I 695 NOTES: 1 AABC CERTIFIED System SPLIT UNIT TEST Commission 8 Testing,Inc.ing PROJECT: LITCHFIELD EASY STORAGE DATE: 5/24/2023 MANUFACTURER: 'CARRIER TYPE: Heat Pump Split Unit MODEL NUMBER (EVAP): IFX4DNF049 SYSTEM: I'CU 1-3/CU 1-3 MODEL NUMBER(COND): 125HCE448A600 EOUIPMENT LOCATION: CEILING SERIAL NUMBER(EVAP): [3122F04698 AREA SERVED: BASEMENT SERIAL NUMBER(COND): 14122E11451 REQUIRED FINAL TOTAL CFM: 1600 1650 OUTSIDE AIR CFM: 0 0 ESP: 0.50 0.16" DEVICE IN OUT DELTA P FAN 0.09 FILTER -0.07 I REQUIRED FINAL EVAP MOTOR VOLTAGE: I 208,1 486/487/487 EVAPORATIVE MOTOR HP: I 0.75 3/4 EVAPORATIVE MOTOR RPM: 3 SPD SPD 2 EVAPORATIVE MOTOR AMPS: l 6.0 2.6 COMPRESSOR VOLTAGE: 460 ; 486/487/487 COMPRESSOR AMPS: 6.0 3.5/3.9/4.0 CONDENSER AMPS: 0.77 0.65 FAN RPM: I SPD 2 MOTOR SHEAVE: I)I R I C I I)R I V E FAN SHEAVE: BELT SIZE(#OF): CENTER TO CENTER: NOTES: TEMPERATURES EN"TERING LEAN INC DRY BULB: 74 54 WET BULB: 61 48 HEATING(DB ONLY): 74 90 OSA DB OSA WB I 84 1 73 • . . AABC CERTIFIED TERMINAL DEVICE SHEET CommSystems issioning& ��Testing,Inc. PROJECT: LITCHFIELD EASY STORAGE DATE: 5/24/2023 SYSTEM: FCU 1-3 TYPE: SUPPLY REQUIRED PRELIMINARY FINAL ROOM# TERMINAL SIZE Ak RDG CFM RDG CFM RDG CFM BASEMENT 1 12x8 0.66 606 400 589 390 589 390 BASEMENT 2 12x8 0.66 606 400 645 425 645 425 BASEMENT 3 12x8 0.66 606 400 651 430 651 .1;ii BASEMENT 4 12x8 0.66 606 400 611 405 611 4115 TOTAL CFM: 1600 1650 1650 J NOTES: 6 • AABC CERTIFIED -�Systems Commissioning 8 SPLIT UNIT TEST Testing,Inc. PROJECT: LITCHFIELD EASY STORAGE DATE: 5/26/2023 MANUFACTURER: 'CARRIER TYPE: Heat Pump Split Unit MODEL NUMBER (EVAP): IFXDNF049 SYSTEM: FCU 2-1 CU 2-1 MODEL NUMBER(COND): 125HCW448A600 EOUIPMENT LOCATION: ROOF SERIAL NUMBER(EVAP): 12922F05051 AREA SERVED: 1ST FLOOR SERIAL NUMBER(COND): 14122E11458 REQUIRED FINAL TOTAL CFM: 1200 1240 OUTSIDE AIR CFM: 110 105(1) ESP: 0.50 0.14" DEVICE IN OUT DELTA P FAN 0.08 I. I FILTER -0.06 REQUIRED FINAL EVAP MOTOR VOLTAGE: 208/1 487/486/488 EVAPORATIVE MOTOR HP: 0.75 3/4 EVAPORATIVE MOTOR RPM: 3 SPD SPD 2 EVAPORATIVE MOTOR AMPS: 6.0 2.8 COMPRESSOR VOLTAGE: 460 3 487/486/488 COMPRESSOR AMPS: 6.0 3.4/3.7/3.6 CONDENSER AMPS: 0.77 0.69 FAN RPM: SPD 2 MOTOR SHEAVE: I)I R I L I D R I VI FAN SHEAVE: I BELT SIZE(#OF): CENTER TO CENTER: NOTES: TEMPERATURES ENTERING LEAVING (1)OAFA=6"e=0.20 FT2 x 512 FPM=105 CFM DRY BULB: 76 52 WET BULB: 62 47 HEATING(DB ONLY): 72 89 OSA DB OSA RB 84 72 7 • AABC CERTIFIED C,Systems g TERMINAL DEVICE SHEET Commissionin & ow Testing,Inc. PROJECT: LITCHFIELD EASY STORAGE DATE: 5/24/2023 SYSTEM: FCU 2-I TYPE: SUPPLY REQUIRED PRELIMINARY FINAL ROOM# TERMINAL SIZE Ak RDG CFM RDG CFM RDG CFM 1ST FLOOR 1 12x8 0.66 606 400 639 420 639 420 1ST FLOOR 2 12x8 0.66 606 400 624 410 624 410 1ST FLOOR 3 12x8 0.66 606 400 622 410 622 410 TOTAL CFM: 1200 1240 1240 NOTES: 8 • AABC CERTIFIED Systems Commi SPLIT UNIT TEST s & Testing,Inc.sioning PROJECT: LITCHFIELD EASY STORAGE DATE: 5/26/2023 MANUFACTURER: 'CARRIER TYPE: Heat Pump Split Unit MODEL NUMBER (EVAP): IFXDNF037 SYSTEM: FCU 2-2/CU 2-2 MODEL NUMBER(COND): I25HCE436A610 EOUIPMENT LOCATION: ROOF SERIAL NUMBER(EVAP): I0522F25571 AREA SERVED: 1ST FLOOR SERIAL NUMBER(COND): 1922E03383 REQUIRED FINAL TOTAL CFM: 1200 1275 OUTSIDE AIR CFM: 75 75(1) ESP: 0.50 0.18" DEVICE IN OUT DELTA P FAN 0.1 FILTER I -0.08 I I REQUIRED FINAL EVAP MOTOR VOLTAGE: 208/1 I 489/484/486 EVAPORATIVE MOTOR HP: 0.75 3/4 EVAPORATIVE MOTOR RPM: 3 SPD SPD 2 EVAPORATIVE MOTOR AMPS: 4.1 2.8 COMPRESSOR VOLTAGE: 460/3 489/484 486 COMPRESSOR AMPS: 3.85 2.3/1.8/2.0 CONDENSER AMPS: 0.60 0.55 FAN RPM: SPD 2 MOTOR SHEAVE: DIRECT DRIVE FAN SHEAVE: BELT SIZE(#OF): I CENTER TO CENTER: NOTES: TEMPERATURES ENTERING LEANING (1)OAFA=6"0=0.20 FT2 x 378 AFPM=75 CFM DRY BULB: 75 ;5 WET BULB: 61 49 HEATING(DB ONLY): L. 75 88 OSA DB OSA WB 84 I 73 9 AABC CERTIFIED C,_Systems TERMINAL DEVICE SHEET Commissioning& Testing,Inc. PROJECT: LITCHFIELD EASY STORAGE DATE: 5/24/2023 SYSTEM: FCU 2-2 TYPE: SUPPLY REQUIRED PRELIMINARY FINAL ROOM# TERMINAL SIZE Ak RDG CFM RDG CFM RDG CFM LOBBY I 12x8 0.66 454 300 185 125 488 320 LOBBY 2 12x8 0.66 454 300 163 105 475 3 I RR 3 4 1.0 50 90 RR 4 4 1.0 50 65 > LOBBY 5 12x8 0.66 454 300 750 495 479 31 BREAK RM 6 8 1.0 200 245 21 TOTAL CFM: 1200 1125 1275 NOTES: 10 AABC CERTIFIED C Systems SPLIT UNIT TEST Commissionin & Testing,Inc. g PROJECT: LITCHFIELD EASY STORAGE DATE: 5/26/2023 MANUFACTURER: 'CARRIER TYPE: Heat Pump Split Unit MODEL NUMBER (EVAP): IFXDNF037 SYSTEM: FCU 2-3 CU 2-3 MODEL NUMBER(COND): I25HCE436A610 EOUIPMENT LOCATION: ROOF SERIAL NUMBER(EVAP): '0522F25013 AREA SERVED: 2ND FLOOR SERIAL NUMBER(COND): 1922E03381 REQUIRED FINAL TOTAL CFM: 1600 1685 OUTSIDE AIR CFM: 0 0 ESP: 0.50 0.13" DEVICE IN OUT DELTA P FAN 0.07 I Iiimmutri -0.06 I I REQUIRE!) FINAL EVAP MOTOR VOLTAGE: 208/1 486/487/488 EVAPORATIVE MOTOR HP: 0.75 3/4 EVAPORATIVE MOTOR RPM: L 3 SPI) SPD 2 EVAPORATIVE MOTOR AMPS: 4.1 2.1 COMPRESSOR VOLTAGE: 460 3 486/487/488 COMPRESSOR AMPS: 3.85 1.9/1.7'2.1 CONDENSER AMPS: 0.60 0.47 FAN RPM: I SPD 2 MOTOR SHEAVE: I)0/I CT DRIVE FAN SHEAVE: BELT SIZE(#OF): CENTER TO CENTER: NOTES: TEMPERATURES ENTERING LEAVING DRY BULB: 76 54 WET BULB: 63 49 HEATING(DB ONLY): 76 90 OSA DB OSA WB 84 I 72 II AABC CERTIFIED --.. SystCommissems Testing,Inc.ioning 8 TERMINAL DEVICE SHEET PROJECT: LITCHFIELD EASY STORAGE DATE: 5/24/2023 SYSTEM: FCU 2-3 TYPE: SUPPLY REQUIRED PRELIMINARY FINAL ROOM# TERMINAL SIZE Ak RDG CFM RDG CFM RDG CFM 1ST FLOOR 1 12x8 0.66 606 400 448 295 617 410 i 1ST FLOOR 2 12x8 0.66 606 400 687 455 625 415 1ST FLOOR 3 12x8 0.66 606 400 786 520 664 440 1ST FLOOR 4 12x8 0.66 606 400 627 415 635 420 TOTAL CFM: 1600 1685 1685 NOTES: 12 • AABC CERTIFIED systes SPLIT UNIT TEST ommissioning m &Testing,tnc. PROJECT: LITCHFIELD EASY STORAGE DATE: 5/26/2023 MANUFACTURER: [CARRIER TYPE: Heat Pump Split Unit MODEL NUMBER (EVAP): (FX4DNF037 SYSTEM: FCU 3-1/CU 3-1 n1ODEL NUMBER(COND): 125 HCE436A610 EOUIPMENT LOCATION: ROOF SERIAL NUMBER(EVAP): 10522E25078 AREA SERVED: 2ND FLOOR SERIAL NUMBER(COND): 1922E 18100 REQUIRED FINAL TOTAL CFM: 1200 1225 OUTSIDE AIR CFM: 75 80(1) ESP: 0.50 0.09" DEVICE 1N OUT DELTAP FAN 0.05 IFILTER -0.04 REQUIRED FINAL EVAP MOTOR VOLTAGE: ( 208/1 484/486/486 EVAPORATIVE MOTOR HP: 0.50 1/2 EVAPORATIVE MOTOR RPM: 3 SPD SPD 2 EVAPORATIVE MOTOR AMPS: 4.1 j 2.0 COMPRESSOR VOLTAGE: 460/3 484/486%486 COMPRESSOR AMPS: 3.85 190 CONDENSER AMPS: 0.60 0.45 FAN RPM: SPD 2 MOTOR SHEAVE: DIRECT DRIVE FAN SHEAVE: BELT SIZE(#OF): CENTER TO CENTER: NOTES: TEM PERATURES ENTERING LEAVING (I)OAFA=6"e=0.20 FT2 x 404 AFPM=80 CFM DRY BULB: 75 r 55 WET BULB: 6; 3tt HEATING(DB ONLY): 75 N8 OSA DB OSA WB 84 ( 72 13 AABC CERTIFIED Systems mmiss 8,ionin TERMINAL DEVICE SHEET o Testing,Inc. g PROJECT: LITCHFIELD EASY STORAGE DATE: 5/24/2023 SYSTEM: FCU 3-1 TYPE: SUPPLY REQUIRED PRELIMINARY FINAL ROOM# TERMINAL SIZE Ak RDG CFM RDG CFM RDG CFM 2ND FLOOR 1 12x8 0.66 606 400 593 390 593 390 2ND FLOOR 2 12x8 0.66 606 400 652 430 652 430 2ND FLOOR 3 12x8 0.66 606 400 613 405 613 41)5 TOTAL CFM: 1200 1225 1225 NOTES: 14 • AABC CERTIFIED C,Systems SPLIT UNIT TEST Commissionin & Testing,Inc. g PROJECT: LITCHFIELD EASY STORAGE DATE: 526/2023 MANUFACTURER: 'CARRIER TYPE: Heat Pump Split Unit MODEL NUMBER (EVAP): IFX4DNF049 SYSTEM: FCU 3-2/CU 3-2 MODEL NUMBER(COND): I25HCE448A600 EOUIPMENT LOCATION: ROOF SERIAL NUMBER(EVAP): 12522E01843 AREA SERVED: 2ND FLOOR SERIAL NUMBER(COND): 14122E 11452 REQUIRED FINAL TOTAL CFM: 1600 1690 OUTSIDE AIR CFM: 75 80(1) • I ESP: 0.50 0.18" DEVICE IN OUT DELTA P FAN 0.1 FILTER -0.08 REQUIRED FINAL EVAP MOTOR VOLTAGE: 208/1 489/486/488 EVAPORATIVE MOTOR HP: I 0.75 3/4 EVAPORATIVE MOTOR RPM: 3 SPD SPD 2 EVAPORATIVE MOTOR AMPS: 6.0 2.9 COMPRESSOR VOLTAGE: 460/3 489/486/488 COMPRESSOR AMPS: 6.0 2.9/3.3/3.0 CONDENSER AMPS: 0.77 0.66 FAN RPM: 1 SPD 2 MOTOR SHEAVE: DIRECT DRIVE FAN SHEAVE: BELT SIZE(#OF): CENTER TO CENTER: NOTES: TEMPERATURES ENTERING LEAVING (I)OAFA=6"e=0.20 FT2 x 414 AFPM=80 CFM DRY BULB: 76 54 WET BULB: 6 I 50 HEATING(DB ONLY): I 70 89 OSA DB OSA WB 84 I 74 15 AABC CERTIFIED Systems(-CommsmfltnY& TERMINAL DEVICE SHEET ▪ Testing.Inc. PROJECT: LITCHFIELD EASY STORAGE DATE: 5/24/2023 SYSTEM: FCU 3-2 TYPE: SUPPLY REQUIRED PRELIMINARY FINAL ROOM# TERMINAL SIZE Ak RDG CFM RDG CFM RDG ('FV1 2ND FLOOR 1 12x8 0.66 606 400 622 410 634 42( 2ND FLOOR 2 12x8 0.66 606 400 605 400 612 40; 2ND FLOOR 3 12x8 0.66 606 400 670 440 664 4 2ND FLOOR 4 12x8 0.66 606 400 674 445 653 410 TOTAL CFM: 1600 1695 169O NOTES: I t, • . . AABC CERrIFlED Systems SPLIT UNIT TEST "' Commio 8 Testing iss,I ncning. PROJECT: LITCHFIELD EASY STORAGE DATE: 5/26/2023 MANUFACTURER: (CARRIER TYPE: Heat Pump Split Unit MODEL NUMBER (EVAP): IFX4DNF049 SYSTEM: FCU 3-3/CU 3-3 MODEL NUMBER(COND): 125HCE448A600 EOUIPMENT LOCATION: ROOF SERIAL NUMBER(EVAP): I2922F05046 AREA SERVED: 2ND FLOOR SERIAL NUMBER(COND): 14422E21705 REQUIRED FINAL TOTAL CFM: 1600 1670 OUTSIDE AIR CFM: 75 80(1) ESP: 0.50 0.18" DEVICE IN OUT DELTA P FAN 0.11 I I FILTER -0.7 J REQUIRED FINAL EVAP MOTOR VOLTAGE: 208/1 488/489/488 EVAPORATIVE MOTOR HP: 0.75 3/4 EVAPORATIVE MOTOR RPM: 3 SPD SPD 2 EVAPORATIVE MOTOR AMPS: 6.0 3.1 COMPRESSOR VOLTAGE: 460/3 J 488/489'488 COMPRESSOR AMPS: 6.0 2.9/3.3/3.1 CONDENSER AMPS: 0.77 0.65 FAN RPM: ( SPD 2 MOTOR SHEAVE: DIRECT DRIVE FAN SHEAVE: BELT SIZE(#OF): CENTER TO CENTER: NOTES: TEMPERATURES ENI'ER1NG LEAN INC (I)OAFA=6"0=0.20FT2x397 Al-PM=80CFM DRY BULB: 76 53 WET BULB: 6; 49 HEATING(DB ONLY): 76 88 OSA DE OSA WR 84 I 74 17 • . , AABC CERTIFIED Systems'-Commissioning& TERMINAL DEVICE SHEET ▪ Testing,Inc. PROJECT: LITCHFIELD EASY STORAGE DATE: 5 24 2023 SYSTEM: I'Cl: 3-3 TYPE: SI IPPI V REQUIRED PRELIMINARY FINAL ROOM# TERMINAL SIZE Alt RDG CFM RDG CFM RDC CFM 2ND FLOOR 1 12x8 0.66 606 400 612 405 623 410 2ND FLOOR 2 12x8 0.66 606 400 598 395 6C2 41)u 2ND FLOOR 3 12x8 0.66 606 400 639 420 641 425 2ND FLOOR 4 12x8 0.66 606 400 688 455 661 415 TOTAL CFM: 1600 1675 167o NOTES: I� AABC CERTIFIED Systems SPLIT UNIT TEST Commissioning 8 Testing,Inc. PROJECT: LITCHFIELD EASY STORAGE DATE: 5/26/2023 MANUFACTURER: 1ARRIER TYPE: Heat Pump Split Unit MODEL NUMBER (EVAPI: IFX4DNF049 SYSTEM: FCU 3-4/CU 3-4 MODEL NUMBER(COND): (25HCE448A600 EOUIPMENT LOCATION: ROOF SERIAL NUMBER(EVAP): I2522F01861 AREA SERVED: 2ND FLOOR SERIAL NUMBER(COND): 14422E21468 REQUIRED FINAL TOTAL CFM: 1600 1615 OUTSIDE AIR CFM: 75 75(1) ESP: 0.50 0.1 5" 1)E\ ICE IN OUT DELTA P FAN 0.09 FILTER -0.06 REQUIRED FINAL EVAP MOTOR VOLTAGE: 208'1 487/488/485 EVAPORATIVE MOTOR HP: 0.75 3/4 EVAPORATIVE MOTOR RPM: 3 SPD SPD 2 EVAPORATIVE MOTOR AMPS: 6.0 3.2 COMPRESSOR VOLTAGE: 460/3 487/488 485 COMPRESSOR AMPS: 6.0 2.8/3.1 CONDENSER AMPS: 0.77 0.65 FAN RPM: I SPD 2 MOTOR SHEAVE: DIRECT DRIVE FAN SHEAVE: BELT SIZE(#OF): CENTER TO CENTER: NOTES: TEMPERATURES EN l F:12ING LEAVING (1)OAFA=6"e=0.20 FT2 x 389 AFPM=75 CFM DRY BULB: 77 52 WET BULB: 62 49 HEATING(DB ONLY): 77 88 OSA DB OSA RB I 84 I 74 19 AABC CERTIFIED ` Systems Testing,Inc. g miss &ionin TERMINAL DEVICE SHEET PROJECT: LITCHFIELD EASY STORAGE DATE: 5/24/2023 SYSTEM: FCU 3-4 TYPE: SUPPLY REQUIRED PRELIMINARY FINAL ROOM# TERMINAL SIZE Ak RDG CFM RDG CFM RDG CFM 2ND FLOOR 1 12x8 0.66 606 400 623 410 623 410 2ND FLOOR 2 12x8 0.66 606 400 630 415 630 41 2ND FLOOR 3 12x8 0.66 606 400 589 390 589 ,01) 2ND FLOOR 4 12x8 0.66 606 400 602 400 602 406 TOTAL CFM: 1600 1615 1615 NOTES: 'u • AABC CERTIFIED Csmtemnl SPLIT UNIT TEST Coioning 8 Testing,Inc. PROJECT: LITCHFIELD EASY STORAGE DATE: 5-'26/2023 MANUFACTURER: CARRIER TYPE: Heat Pump Split Unit MODEL NUMBER (EVAP): (FX4DNF049 SYSTEM: FCU 3-5/CU 3-5 MODEL NUMBER(COND): I25HCE448A600 EOUIPMENT LOCATION: ROOF SERIAL NUMBER(EVAP): I3022F13803 AREA SERVED: 2ND FLOOR SERIAL NUMBER(COND): 14122E11448 REQUIRED FINAL TOTAL CFM: 1600 1645 OUTSIDE AIR CFM: 75 80(1) ESP: 0.50 0.19" DEVICE IN OUT DELTA P FAN 0.1 I FILTER -0.09 REQUIRED FINAL EVAP MOTOR VOLTAGE: 208/1 487/486/488 EVAPORATIVE MOTOR HP: 0.75 3/4 EVAPORATIVE MOTOR RPM: 3 SPD SPD 2 EVAPORATIVE MOTOR AMPS: 6.0 3.0 COMPRESSOR VOLTAGE: 460/3 487/486i488 COMPRESSOR AMPS: 6.0 2.8/3.0/3.1 CONDENSER AMPS: 0.77 0.64 FAN RPM: SPD 2 MOTOR SHEAVE: 1)IRI 11)RIVI FAN SHEAVE: I BELT SIZE(#OF): CENTER TO CENTER: NOTES: TEMPERATURES ENTERING LEAVING (I)OAFA=6"e=0.20 FT2 x 401 AFPM=80 CFM DRY BULB: 76 52 WET BULB: (U 46 HEATING(DB ONLY): 76 90 OSA DB OSA WB 84 I 74 21 AABC CERTIFIED Systems ioning& TERMINAL DEVICE SHEET Testing,Inc. PROJECT: LITCHFIELD EASY STORAGE DATE: 5/24/2023 SYSTEM: FCU 3-5 TYPE: SUPPLY" REQUIRED PRELIMINARY FINAL ROOM# TERMINAL SIZE Ak RDG CFM RDG CFM RDG CFM 2ND FLOOR 1 12x8 0.66 454 300 495 325 487 320 2ND FLOOR 2 12x8 0.66 606 400 639 420 618 li).; 2ND FLOOR 3 12x8 0.66 378 250 404 265 388 2 5 2ND FLOOR 4 12x8 0.66 606 400 585 385 611 405 2ND FLOOR 5 12x8 0.66 378 250 523 345 398 260 TOTAL CFM: 1600 1740 1645 7 NOTES: 22 AABC CERTIFIED Systems SPLIT UNIT TEST Commissioning Testing,Inc. PROJECT: LITCHFIELD EASY STORAGE DATE: 5 26/2023 MANUFACTURER: JLENNOX TYPE: MODEL NUMBER (EVAP): 140MAHBQ18XA3 SYSTEM: IU-l/OU-1 MODEL NUMBER(COND): 138MARBQ18AA301 EOUIPMENT LOCATION: ROOF SERIAL NUMBER(EVAP): 1341 V 14064 AREA SERVED: MECH ROOM SERIAL NUMBER(COND): )0822V33579 REQUIRED FINAL TOTAL CFM: 442 -442 OUTSIDE AIR CFM: N/A N/A ESP: N/A N/A DEVICE IN UUT DELTA P FAN FILTER I II I REQUIRED FINAL EVAP MOTOR VOLTAGE: 208/1 210/1 EVAPORATIVE MOTOR HP: NOT LISTED NOT LISTED EVAPORATIVE MOTOR RPM: VARIABLE USER CONTROLLED EVAPORATIVE MOTOR AMPS: 3.I) 1.8 COMPRESSOR VOLTAGE: 20 I 210 COMPRESSOR AMPS: I 7.8 CONDENSER AMPS: I 0 0.70 FAN RPM: USER CONTROLLED MOTOR SHEAVE: DIRECT DRIVE FAN SHEAVE: BELT SIZE(#OF): CENTER TO CENTER: 1 NOTES: TEMPERATURES ENTERING LEAVING DRY BULB: ( 70 54 WET BULB: 53 49 HEATING(DB ONLY): N.A N/A Us t DB OSA WB NA I_ N A AABC CERTIFIED Systems SPLIT UNIT TEST Commissioning 8 Testing,Inc. PROJECT: LITCHFIELD EASY STORAGE DATE: 5/26/2023 MANUFACTURER: 'LENNOX TYPE: MODEL NUMBER (EVAP): (MWMC018S4 SYSTEM: MODEL NUMBER(COND): IMPC018S4S EOUIPMENT LOCATION: ROOF SERIAL NUMBER(EVAP): IS6922H01080 AREA SERVED: ELEVATOR ROOM SERIAL NUMBER(COND): IS6922F08155 REQUIRED FINAL TOTAL CFM: 600 +/-600 OUTSIDE AIR CFM: N/A N/A ESP: N/A N/A DEVICE IN OUT I)EI.TA P FAN FILTER _ I REQUIRED FINAL EVAP MOTOR VOLTAGE: 208/1 209/I EVAPORATIVE MOTOR HP: NOT LISTED NOT LISTED EVAPORATIVE MOTOR RPM: VARIABLE I( USER CONTROLLED EVAPORATIVE MOTOR AMPS: 2.0 COMPRESSOR VOLTAGE: ?ilx I 209/I COMPRESSOR AMPS: 1;.(1 6.9 CONDENSER AMPS: 0.44 0.44 FAN RPM: USER CONTROLLED MOTOR SHEAVE: DIRECT DRIVE FAN SHEAVE: BELT SIZE(#OFI: CENTER TO CENTER: NOTES: TEMPERATURES EN I'ERING LEAVING DRY BULB: 70 52 WET BULB: 53 47 HEATING(DB ONLY): I N A N/A OSA DB OSA WB N/A N/A 24 AABC CERTIFIED e Systems Commissioning& CEILING MOUNTED EXHAUST FANS Testing,Inc. PROJECT:LITCHFIELD EASY STORAGE DATE: 2023-05-24T00:00:00 FAN# MODEL# ' ROOM SERVED MANUFACTURER SERIAL# CFM HP VOLTS AMPS RPM* EF-1 SP-A90 RR REQUIRED 75 15W 120/1 0.4 1 SPD GREENHECK 20461585 ACTUAL 80 15W 113/I 0.17 HIGH EF-2 SP-A90 REQUIRED 75 15W 120/1 0.4 1 SPD RR GREENHECK 20461603 ACTUAL 80 15W 1121 0.17 HIGH EF-3 SP-A90 JAN REQUIRED 75 15W 120 1 0.4 1 SPD GREENHECK 20461402 ACTUAL 75 15W 112/1 0.17 HIGH *The fan rpm is the same as the motor rpm since the fan is direct drive. **The static pressures for these fans are not accessible. NOTES 25