SMOKE DETECTOR INSPECTION
MIMI
AABC
Systems Commissioning & resting, Inc.
16772 W.Bell Rd. Ste 110-432 Surprise,AZ 85374 (520)884-4792
Dustin M.Fielden,President Toll Free: (866)-334-7119 AZ ROC License#081448E-39
Associated Air Balance Council
AABC
C .
PROJECT:LITCHFIELD EASY STORAGE PAGE:2 OF 2
/ma wSS:5960 . NDALE,AZ PATE:5/31/2023
PERMIT: BY:DUSTIN FIELDEN
Smoke detectors have been inspected per the tasks listed.Exceptions to a passing condition are identified with a
numbered note.Performance testes results are for equipment function on date tested.If the building owner or any
representative of the building owner observes or believes a deficiency is present,modifications have been made,or six
months have passed since this testing,the system must be re-inspected and retested.
MANUFACTURER:AIR PRODUCTS AND CONTROLS MODEL:SL-2000-P
UNIT DUCT SAMPLE RATED TEST FAN ALARM ALARM ALARM
AND SIZE TUBE A P"WC A P SHUT VISUAL AUDIBLE FIRE
LOCATION W x H LENGTH MIN-*MAX "WC DOWN PANEL
FCU 3-I 20x20 18" 0.01-1.11" o(Li- 1 ✓ N/A ✓
RETURN
FCU 3-2 ✓ ✓ N/A ✓
RETURN 20x23 i R" 0.01 - I I I" n U.
FCU 3-3 ✓ V N/A ✓
RETURN 20x23 18" 0.01 -1.11' 0..03"
FCU 3-4 20x23 I R" 0.01 -1.1 I" 0.04" ✓ ✓ N/A ✓
RETURN
•
FCU 3-5 18x14 18" 0.01-1.11" U.U�3 ✓ ✓ N/A ✓
RETURN
INSPECTION TASKS(AS APPLICABLE)
DELTA PRESSURE: As measured across the detector sampling tubes.
FAN SHUT DOWN: Tested for immediate shut down when detector is challenged with canned smoke.
Fan shut down is STAND ALONE-OR-CLOR%L.
VISUAL ALARM: Lighting of remote test/indicator unit(not required if detector is visible from floor.)
AUDIBLE ALARM: Sounding of remote test/indicator unit(not required in all municipalities.)
FIRE PANEL: Alarm reports to central fire panel(remote test/indicator unit not then required.)
NOTES:
OANII% Onirt. d T
F ��P\R,.,,,re s4.
7
•
it-ii ,,,itx •
b
e O e •2t-Q�1�0C
4Jlin M fie\`'
4
i
411.16.
SMOKE DETECTOR INSPECTION
AA BC
Systems Commissioning & Testing, Inc.
16772 W. Bell Rd. Ste 110-432 Surprise,AZ 85374 (520)884-4792
Dustin M. Fielden,President Toll Free: (866)-334-7119 AZ ROC License#081448L-39
Associated Air Balance Council
AABC
PROJECT:LITCHFIELD EASY STORAGE PAGE: 1 OF 2
ADDRESS:5960 N LITCHFIELD RD.GLENDALE.AZ DATE:5/31/2023
PERMIT: BY:DUSTIN FIELDEN
Smoke detectors have been inspected per the tasks listed.Exceptions to a passing condition are identified with a
numbered note.Performance testes results are for equipment function on date tested.if the building owner or any
representative of the building owner observes or believes a deficiency is present,modifications have been made,or six
months have passed since this testing,the system must be re-inspected and retested.
MANUFACTURER:AIR PRODUCTS AND CONTROLS MODEL:SL-2000-P
UNIT DUCT SAMPLE RATED TEST FAN ALARM ALARM ALARM
AND SIZE TUBE A P"WC A P SHUT VISUAL AUDIBLE FIRE
LOCATION W x H LENGTH MIN—►MAX "WC DOWN PANEL
FCU 1-1 20x23 18" 0.01 - 1 I I' 0.03" ✓ ✓ N/A 1(
RETURN
FCU 1-2 20x23 18" 0.0l - 1.11' 0.04" ✓ ✓ N/A ✓
RETURN
—
FCU 1-3
20x23
1( 1( N/A 1(RETURN I R" 0.01 - i l. I" 0..03"
FCU2-I ,l�y2x 18" 0.01 - 1.11" 0.0��' ✓ ✓ N/A 1(
RETURN
FCU 2-2 �/ V/ N/A ✓
RETURN I�v l 1 �" I1.01 - l.l I" 11.11a"
FCU2-3 (021) 18" 0.01 -1.1 I' 0.O5" ✓ ✓ N/A ✓
RETURN
INSPECTION TASKS(AS APPLICABLE)
DELTA PRESSURE: As measured across the detector sampling tubes.
FAN SHUT DOWN: Tested for immediate shut down when detector is challenged with canned smoke.
Fan shut down is STAND ALO .
VISUAL ALARM: Lighting of remote test/indicator unit(not required if detector is visible from floor.)
AUDIBLE ALARM: Sounding of remote test/indicator unit(not required in all municipalities.)
FIRE PANEL: Alarm reports to central fire panel(remote test/indicator unit not then required.)