HomeMy WebLinkAbout89393 cg3g3 SMOKE DETECTOR INSPECTION mig �� ARIZONA AIR BALANCE COMPANY �� VNIIII 624 S. PERRY LANE, SUITE 101 • TEMPE, ARIZONA • 480.966.2001 AABC- MEMBER OF ASSOCIATED AIR BALANCE COUNCIL PROJECT: Arrowhead Creekside - Building G PAGE: 1 OF 1 ADDRESS: 7200 W. Bell Rd, Glendale, AZ 85308 DATE: 7/30/2015 PERMIT: BLD89424, BLD89397, BLD89346 BY: VL/MBJ Smoke detectors have been inspected per the tasks listed. Variations or exceptions to a passing condition are identified with a numbered note. Performance tests are for equipment function on date tested. If the building owner or any representative of the building owner observes or believes a deficiency is present, modifications have been made, or six months have passed since this testing, the system must be reinspected and retested. MANUFACTURER: FireX MODEL: 2650-560 UNIT DUCT SAMPLE RATED TEST FAN ALARM ALARM TEST / AND SIZE TUBE A P "WC A P SHUT VISUAL FIRE DATE LOCATION W x H LENGTH MIN MAX "WC DOWN AUDIBLE PANEL RTU-1 (S) Pass 7/30/2015 Supply Air 20"O 12" 0.01 1.20 0.09 Pass """"""'NIA............. (1) RTU-2(N) 20"0 12" 0.01 1.20 0.07 Pass NSA (1) 7/30/2015 Supply Air .............................................. ............................................. INSPECTION TASKS (AS APPLICABLE) DELTA PRESSURE: As measured across the detector sampling tubes. FAN SHUT DOWN: Tested for immediate shut down when detector is challenged with canned smoke. Fan shut down is STAND ALONE VISUAL ALARM: Lighting of remote test/indicator unit:Green pilot,amber trouble,red alarm. (Remote test/indicator unit not required if detector is visible from floor). AUDIBLE ALARM: Sounding of remote test/indicator unit(not required in all municipalities). FIRE PANEL ALARM: Alarm reports to central fire panel(remote test/indicator unit not then required). NOTES (1) Duct detector does not report to fire panel. P<gatance cta. tAct BAL 4, % J/ 6'Pror. A. See