SMOKE DETECTOR INSPECTION mig
�� ARIZONA AIR BALANCE COMPANY ��
VNIIII
624 S. PERRY LANE, SUITE 101 • TEMPE, ARIZONA • 480.966.2001 AABC-
MEMBER OF ASSOCIATED AIR BALANCE COUNCIL
PROJECT: Arrowhead Creekside - Building G PAGE: 1 OF 1
ADDRESS: 7200 W. Bell Rd, Glendale, AZ 85308 DATE: 7/30/2015
PERMIT: BLD89424, BLD89397, BLD89346 BY: VL/MBJ
Smoke detectors have been inspected per the tasks listed. Variations or exceptions to a passing
condition are identified with a numbered note. Performance tests are for equipment function on
date tested. If the building owner or any representative of the building owner observes or believes
a deficiency is present, modifications have been made, or six months have passed since this
testing, the system must be reinspected and retested.
MANUFACTURER: FireX MODEL: 2650-560
UNIT DUCT SAMPLE RATED TEST FAN ALARM ALARM TEST /
AND SIZE TUBE A P "WC A P SHUT VISUAL FIRE DATE
LOCATION W x H LENGTH MIN MAX "WC DOWN AUDIBLE PANEL
RTU-1 (S) Pass 7/30/2015
Supply Air
20"O 12" 0.01 1.20 0.09 Pass """"""'NIA............. (1)
RTU-2(N) 20"0 12" 0.01 1.20 0.07 Pass NSA (1) 7/30/2015
Supply Air
..............................................
.............................................
INSPECTION TASKS (AS APPLICABLE)
DELTA PRESSURE: As measured across the detector sampling tubes.
FAN SHUT DOWN: Tested for immediate shut down when detector is challenged with canned smoke.
Fan shut down is STAND ALONE
VISUAL ALARM: Lighting of remote test/indicator unit:Green pilot,amber trouble,red alarm.
(Remote test/indicator unit not required if detector is visible from floor).
AUDIBLE ALARM: Sounding of remote test/indicator unit(not required in all municipalities).
FIRE PANEL ALARM: Alarm reports to central fire panel(remote test/indicator unit not then required).
NOTES
(1) Duct detector does not report to fire panel.
P<gatance
cta. tAct BAL 4, %