HomeMy WebLinkAbout0000 (3) T4z6t A ti4 E414.4.ce 5t4/ -
MI
HVAC Testing • Analysis • Balance • Energy Survey • Systems Commissioning • Clean Room Testing
Test & Balance Analysis Report
For
Endoscopy Center Renovation
Banner Thunderbird
5 823 W. Eugie Rd., Ste 1 & 2
Glendale, AZ
Date: December 29th 2009
Architect: Cassetty Architecture
Mechanical Engineer: Entech Engineering Inc.
Prepared For: HACI Mechanical Contractors
G9‘plt Balagee
�rc�0 p1R BA/4
� co
sae A H aid\°
29215
�C
16055 N.Dial Blvd.,Ste.#8 Scottsdale, AZ 85260
(623) 492-0831 Fax: (623) 492-0845
ROC189960 L-05
Aok
'I' A Tee-4 ,641 /4;4 getim-ta SW
tptc.
' AABC
Thunderbird Endoscopy
Table of Contents
Unit Number Description Location Page
AC-4 Package/Split System DX Test M2.1 1, 2
Reduced print
_ L._, Td4 A SW, Imo. 0
AABC Page 1
PACKAGE / SPLIT SYSTEM DX TEST
PROJECT: Thunderbird Endoscopy
SYSTEM: ACU-4 DATE: 12-28-09
LOCATION: M2.1 TECHNICIAN: JC
UNIT # AC-4
MANUFACTURER Trane
MODEL# WSC048
DESIGN DATA FINAL DATA
TOTAL CFM 1350 1405
RETURN CFM / OSA CFM 1150 200 1200 205
FAN STAT. PRESS: EXTERNAL 1.00
FILTER IN / FAN OUT - .26 + .74
MOTOR: HP 1.0 1.0
MOTOR: RPM 1725 1743
MOTOR: VOLTS / PH 208 3 208 3
MOTOR: AMPS 4.0 4.0 4.0 3.2 3.3 3.2
FAN RPM 1061
COMPRESSOR:AMPS 16.0 16.0 16.0 7.2 7.6 7.3 _
CONDENSER FAN: AMPS 2.5 2.2
MOTOR SHEAVE 1 VL30 x 5/8
FAN PULLEY AK49 x 3/4
NO. BELTS / SIZE AX-26
TEMPERATURE TEST ENTERING LEAVING DELTA "T"
COOLING TEMP.DB 74.3 57.3 17.0
COOLING RELATIVE HUMIDITY% 29.7 55.4
NOTES:
TT A $ 5W f
AABC Page 2
AIR DISTRIBUTION TEST
PROJECT: Thunderbird Endoscopy
ASSOC'D SYS: AC-4 Supply / Return DATE: 12-28-09
LOCATION: M2.1 TECHNICIAN: JC
TERMINAL DESIGN PRE-LIM FINAL
ROOM NO. SIZE" "K" FPM CFM TEST FPM CFM NOTES
1 12 475 375 485
2 10 300 235 305
3 10 300 255 320
4 12 275 405 295
Supply Total 1350 1270 1405
TERMINAL DESIGN PRE-LIM FINAL
ROOM NO. SIZE" "K" FPM CFM TEST FPM CFM NOTES
1 24 x 12 350 265 370
_ 2 24 x 12 350 285 390
3 24 x 24 450 345 440
Return Total 1150 895 1200
NOTES:
1. Return CFM changed to accommodate OSA.
e 'er W f r / .
HVAC Testing-Analysis-Balance - System Commissioning
Duct Smoke Detector Test Report
For
Endoscopy Center TI
Banner Thunderbird
583 W. Eugie Rd . , Ste 1 & 2
Glendale, AZ
Date: December 29, 2009
Prepared For: HACI Mechanical Contractors
p,\r Balance
rc�° \R BA(4�
i 0
to Z
• r •
°e A. Ha06
292'.5
AABC
16055 N. Dial Blvd.. Ste. 8 Scottsdale, AZ 85260
Phone: (623) 492-0831 Fax: (623)492-0845
ROC 189960 L-05
Tk/ 4ASaSW, 11 AI I\
16055 N. Dial Blvd., Ste. #8
Scottsdale, AZ 85260 • (623) 492-083111111,
,4.4ec
SMOKE DETECTOR INSPECTION
PROJECT: Endoscopy Center TI
Banner Thunderbird PAGE: 1 OF 1
ADDRESS: 583 W. Eugie Rd., Ste 1 & 2 DATE: 12/29/09
ADDRESS: Glendale, AZ BY: Jesse Cox
PERMIT:
Smoke detectors have been inspected per the tasks listed. Exceptions to a passing condition are
identified with a numbered note. Performance tests and inspection are for equipment function on date
tested. If the building owner or any representative of the building owner observes or believes a
deficiency is present, modifications have been made, or six months have passed since this testing,
the system must be retested.
MANUFACTURER:FireX MODEL:2650-560
UNIT - DUCT SAMPLE RATED TEST FAN ALARM ALARM TEST
AND SIZE TUBE A P "WC A P SHUT VISUAL FIRE DATE
SYSTEM H"X W" LENGTH" MIN —+ MAX "WC DOWN AUDIBLE PANEL
AC-4 Yes
13 x 24 24 .01 —• 1.2 .05 Yes No No 12-29-09
Return
INSPECTION TASKS (AS APPLICABLE)
DELTA PRESSURE: As measured across the detector sampling tubes.
FAN SHUT DOWN: Tested for immediate shut down when detector is challenged with canned smoke.
Fan shut down is STAND ALONE.
VISUAL ALARM: Lighting of remote test/indicator unit.Red is alarm.(remote not required if detector is visible
from floor).
AUDIBLE ALARM: Sounding of remote test/indicator unit(not required in all municipalities).
FIRE PANEL ALARM: Alarm reports to central fire panel(remote audible unit not then required).
INSTALLATION: Smoke detector is installed per manufacturers recommendation.YES
NOTES
TIT*_ 1 1
__
..
5w tom. M
HVAC Testing-Analysis-Balance- System Commissioning
Duct Smoke Detector Test Report
For
Endoscopy Center TI
Banner Thunderbird
583 W. Eugie Rd. , Ste 1 & 2
Glendale, AZ
Date: December 29, 2009
Prepared For: HACI Mechanical Contractors
a\or Balance
r AeO�,, B4(4 S
ti. �
G� 7 C
Fe .
�. Z
FA
• o • .
6
4 •03-O�-he.�
ae A. Hand
29215 Allik
1111/
AABC
16055 N. Dial Blvd., Ste. 8 Scottsdale, AZ 85260
Phone: (623) 492-0831 Fax: (623)492-0845
ROC 189960 L-05
TLd4Aga5W, (i . _
- 16055 N. Dial Blvd., Ste. #8
A: Scottsdale, AZ 85260 • (623) 492-0831
SMOKE DETECTOR INSPECTION
PROJECT: Endoscopy Center TI
Banner Thunderbird PAGE: 1 OF 1
ADDRESS: 583 W. Eugie Rd., Ste 1 & 2 DATE: 12/29/09
ADDRESS: Glendale, AZ BY: Jesse Cox
PERMIT:
Smoke detectors have been inspected per the tasks listed. Exceptions to a passing condition are
identified with a numbered note. Performance tests and inspection are for equipment function on date
tested. If the building owner or any representative of the building owner observes or believes a
deficiency is present, modifications have been made, or six months have passed since this testing,
the system must be retested.
MANUFACTURER:FireX MODEL:2650-560
UNIT DUCT SAMPLE RATED TEST FAN ALARM ALARM TEST
AND SIZE TUBE A p "WC A p SHUT VISUAL FIRE DATE
SYSTEM H"X W" LENGTH" MIN MAX "WC DOWN AUDIBLE PANEL
AC-4
Return 13 x 24 24 .01 —a 1.2 .05 Yes Nos No 12-29-09
•
INSPECTION TASKS (AS APPLICABLE)
DELTA PRESSURE: As measured across the detector sampling tubes.
FAN SHUT DOWN: Tested for immediate shut down when detector is challenged with canned smoke.
Fan shut down is STAND ALONE.
VISUAL ALARM: Lighting of remote test/indicator unit. Red is alarm.(remote not required if detector is visible
from floor).
AUDIBLE ALARM: Sounding of remote test/indicator unit(not required in all municipalities).
FIRE PANEL ALARM: Alarm reports to central fire panel(remote audible unit not then required).
INSTALLATION: Smoke detector is installed per manufacturers recommendation.YES
NOTES
4:,
iVIEDICA& TECHNOLOGY ASSOCIATES
�
MEDICAL GAS PIPELINE SYSTEMS S PECI A1..1S S �:l A r Svsteris
Medical Gas Certification
For
Thunderbird Endoscopy Center
5823 W. Eugie
Glendale, Arizona 85304
Completed by: Denise Moutinho
Date Completed: October 26, 2009
11001 North 24th Avenue Ste. 606
Phoenix, Arizona 85029
602-674-5205
•
Medical Gas/Vacuum Systems
` ,; Certification
Performed by:
MTA
11001 North 24th Ave. Ste. 606
Phoenix, Arizona. 85029
Location: Thunderbird Endoscopy Center
5823 W. Eugie
Glendale, AZ 85304
Project: OR# 3 Renovation
Contractor: RKS Plumbing
On this date: Oct. 26, 2009
The following equipment was tested:
Qty Description
02 Oxygen Outlets
03 Vacuum Inlets
00 Medical Air Outlets
00 Nitrous Oxide Outlets
00 Nitrogen Outlets
00 Carbon Dioxide Outlets
00 Evacuation Inlets
00 Lab Air Outlets
00 Helium Outlets
02 Shutoff Valves
01 Area Alarm Panels
00 Master Alarm Panels
00 Vacuum Pumps
00 Medical Air Compressor
00 Manifolds
Inspection is per NFPA 99, 2005 Edition. The findings are attached.
Page 1 REV 02.20.04
MTA Corrections Required
CLINICAL AIR SYSTEMS, INC. HAS INSPECTED THIS SYSTEM
FOR ADHAERENCE TO NFPA 99 GAS AND VACUUM SYSTEMS:
2005 EDITION.
THE FOLLOWING IS A LIST OF CORRECTIONS REQUIRED AT
THIS TIME.
• No discrepancies noted at this time
• Released for patient use
Inspected by: NT-42,tiL
Date: 'T
Page: 2 REV 02.20.04
Testing Quality Assurance
Performed by:
MTA
11001 North 24th Ave. Ste. 606
Phoenix, Arizona. 85029
Any or all of the following equipment may have been used during analysis of the
medical gas systems on this project:
1.NST,Model 2500, Medical Gas Analyzer, Serial Number,257
a. Factory calibration performed—July 2009
2.Trace Analytics, Inc.—Medical Gas System Purity Analysis.
3.OXYCHEQ, Oxygen Analyzer, S/N 0200124—Calibrated to a known Oxygen
Source before Performing tests.
a. Calibration Date: 4-23-09
4.Aerotech Laboratories, Inc. -Nosocomial Suite Analysis.
5.Dwyer# RMB—55, 50 —400 CFH, Flow meter.
6.U.S. Gauge—0—200—PSI Gauge
7.U.S. Gauge—0—0—30" HG Gauge.
8.Ohmic AMM-15, Dew Point Monitor; S/N: 28689,
a. Certificate of Calibration: 7/25/2006
9.Bacharach MGC 100 - N20 Monitor; S/N: HS10109
a. Certificate of Calibration: 8/2006
10. Bacharach MGC 200 - CO2/CO Monitor; S/N: GU5285
a. Certificate of Calibration: 8/2006
Page 3 REV. 8/1/006
Master Alarm Testing Procedures
1. Check for proper location.
2. Establish that power is on Life Safety Branch
3. Establish"Power On" Indication.
4. Establish visual and audible alarms("Push to Test").
5. Check high/low set points for all gases by removing and subjecting each
pressure/vacuum switch to a known source of dry Nitrogen or source gas.
6. Check for proper operation of all Change-Over/Reserve-In-Use alarms for all gases
supplied by manifolds or alternating bulk systems.
7. Check for operation of all reserve alarms.
8. Check operation of high dew point alarm.
9. Check operation of high temperature/high water level alarms.
Area Alarm Testing Procedures
1. Check for proper location.
2. Establish that power is on Life Safety Branch.
3. Establish"Power On" Indication.
4. Establish visual and audible alarms(Push to Test).
5. Establish proper labeling(Per Zone and Gas)
6. Observe existing pressure/vacuum reading of alarm panel for each gas.
7. Observe existing low and high alarm points for each gas.
8. Establish actual line pressure with calibration gauge.
9. Calibrate to actual line pressure per Manufacturer's recommendations.
10. Establish and set high and low points per NFPA and Manufacturer's recommendations.
11. Verify actual alarm set points by removing and subjecting each
pressure/vacuum transducer to a known source of dry nitrogen or source gas.
Page 4 REV 02.20.04
Zone Valve Testing Procedures
1. Check for proper location/condition.
2. Check for proper labeling.
3. Check for leakage.
4. Perform valve test.
5. Properly label valves per rooms or areas controlled.
High Pressure Manifold Testing
Procedures
1. Check for existence of duplex line regulators.
2. Check for source shut off valve and pressure relief valve.
3. Check for changeover from primary to secondary bank.
4. Check for proper setting of primary regulator,line regulators,and change pressure
switch per manufacturer's recommendations.
5. Check for leakage.
Page 5 REV 02.20.04
Outlet Testing Procedures
1. Establish proper labeling of outlet.
2. Check for leakage with proper adapter inserted.
3. Check latching mechanism.
4. Check static pressure. Perform vacuum inlet performance test.
5. Perform cross-connect test.
6. Perform valve test.
7. Perform flow test.
8. Perform piping purge test.
9. Perform piping purity test.
10. Perform operational pressure test.
11. Perform medical gas concentration test.
12. Perform medical air purity test.
13. Perform medical air quality test.
Page 6 REV 02.20.04
Area Alarm Panel
& Zone Valve
Certification Form
Certified by: Denise
Date: 10/26/09
Facility: Thunderbird Endoscopy Center
Zone Valve Location: Corridor outside of OR# 3
See page#5 for explanation of testing procedures
Testing Labeled Valve Pass/
# Procedure Gas Area Serviced Zone/Gas Leaking Failed
1 1-5 Oxy OR# 3 Yes/Yes No Pass
2 1-5 Vac Yes/Yes No Pass
3 1-5
4
5
6
7
Comments:
Area Alarm Location: Corridor outside of OR# 3
See page#4 for explanation of testing procedures
Testing Indicated Labeled Indicated Indicated Visual Audible Pass/
# Procedure Gas Pressure Zone/Gas Low Alarm High Alarm Signal Signal Failed
1 1-11 Oxy 54 Yes/Yes 40 60 Yes Yes Pass
2 1-11 Vac 20 Yes/Yes -12 - Yes Yes Pass
3
4
5
6
7
Comments: Existing
Page 7 REV.02.20.04
---�• Medical Gas Outlet/Inlet
Certification Form
Facility: Thunderbird Endoscopy Center Certified by: Denise
� Date: ]0/26/09
See page#6 for explanation of test
Indicated Detected *Test Indicated Detected *Test
# Room Gas _ Gas Results Comments # Room Gas Gas Results Comments
1 OR#3 Oxy Oxy 1 _ 21
2 Oxy Oxy 1 22
3 Vac Vac 1 _ 23
4 Vac Vac 1 24 _
5 Vac Vac 1 _ 25
6 26
7 27
8 28
9 29
10 30
11 31
12 32
13 33
14 34
15 35
16 36
17 37
18 38
19 39
20 40
*Test results code: 6.Flow pressure(psi/hg)exceeds maximum 12.Drop exceeds maximum
l.Satisfies code requirements 7.Unavailable for testing(room in use) 13.Leaks with flow meter
2.Cross connection 8.Unavailable for testing(obstruction) 14.leaks with probe
3.Static pressure(psi/hg)below minimum 9.Leaking
4.Static pressure(psi/hg)exceeds maximum 10.Incorrect or missing gas identification label
5.Flow rate(LPM)below minimum l 1.Mechanical deficienc
,_ Page: 8 REV. 02.20.04
—
ENGINEERING INC.' RENOVATION. — m>liE
A.CODROImME R E,IE.OM:
DUC E DM R,�, IMI ID Ewlullw. I w..II, WALL LEGEND.
t DIM.IN DUCT WING n NCI SUMO u. MIMING ID"tit OXIIIIE<,,.ILIILEx
�I O.CIDNIwSit S I'll Ii ITEll E MIEEIS.Ilx Rrl[<2D CEILING RAN DO IQI I¢,.1E —- —
LR x .MIN E CCU.SOIE DEMO.. EGIDEMO MINIM oFJLBwa WALL.(2 IR)
1 1.0IxnIx a[ww¢S Mb EW M.Dt rxEls u ESIRD M x.E.c. !ID IY R11f®ED
O EOM.,+rotas rEfE R.RIIiION KITE 1 A 7
a8IOY8 AZ
EJDLVING 0ORRATED PARTITION
.. NEW WAIL
u
r�
. - IEEOEEN .A10.0 CASSETT
Tow I-HOUR RRE MORMON
SEE DeAL 6-A10.0
O u.Lrzs,
H.Pgrat Ilw Sr.¢MMDRD ID DEw Illn-R.R..t LE :DInIIxP'''''IEEE
n51P[D!A In O.r IS rnIIIR-EIEID NDlrr.w fln.ID HH[SRR.
A ac xirecru
47) ® e
EXISTING PRACTIG ME
ON
• 446 XxM MININECINE16 II
NOT IN CONTRACT OM as
„•, ~TL)- • Y WON
- - CREWING
Roo.
WO
i 2/6
1 i —
iED B MOM
.
M
•
H 9 fir lArSI.F. MAR.09,200
:J RE 1 —
. lro , I. mom.. RAMMED —
II 1
I.
YE^ 1 SERVICE VEST
it n •
•
• R:sv�, GLEAN
• auwe i
unTry HO t
NILETY C....... .
1fii Is an rlxI I. - —
•r ..J CLERIC... a�rrE.Ia NOV av+ •- w
/
_ ERDOS(.'CPIC
....... 4 .{...— PROCEDURE —
REC^F11L'M
/ ACP RECOVERY I.
ERTM AII...K 1. I•
- ..
. .. W!rTD1u 1
lseP
• ' 'r-g 1 marrow
•
IM:i
.1 VACUUM
m:iM 1 �.T Ras
i - 0409
H.VA.C. HNAC
EW FLOOR
:4) O NEW FLOOR PLAN
M')1